NORDAC SK 200E Manual
256
BU
0200
GB
9.10 Standardisation of setpoint/actual values
The following table contains details for the standardisation of typical setpoint and actual values. This
information relates to the parameters (P400), (P418), (P543), (P546), (P740) or (P741).
Name
Analog signal
Bus signal
Setpoint
{Function}
Value
range
Standardisation
Value
range
Max.
value
Type 100% =
-100% =
Standardisation
Limit
absolute
Setpoint frequency
{01}
0-10V
(10V=100%)
P104 … P105
(min - max)
±100% 16384
INT
4000
hex
16384
dec
C000
hex
-
16385
dec
4000
hex
*
s
etpoint
[Hz]/P105
P105
Frequency
addition
{02}
0-10V
(10V=100%)
P410 … P411
(min - max)
±200% 32767
INT
4000
hex
16384
dec
C000
hex
-
16385
dec
4000
hex
*
s
etpoint
[Hz]/P411
P105
Frequency
subtraction
{03}
0-10V
(10V=100%)
P410 … P411
(min - max)
±200% 32767
INT
4000
hex
16384
dec
C000
hex
-
16385
dec
4000
hex
*
s
etpoint
[Hz]/P411
P105
Minimum
frequency
{04}
0-10V
(10V=100%)
50Hz*
U
AIN
(V)/10V
0…200% 32767 INT 4000
hex
16384
dec
/ 50Hz*
Bus setpoint/4000
hex
P105
Maximum
frequency
{05}
0-10V
(10V=100%)
100Hz*
U
AIN
(V)/10V
0…200% 32767 INT 4000
hex
16384
dec
/ 100Hz*
Bus setpoint/4000
hex
P105
Actual value
Process controller
{06}
0-10V
(10V=100%)
P105*
U
AIN
(V)/10V
±100% 16384
INT
4000
hex
16384
dec
C000
hex
-
16385
dec
4000
hex
*
s
etpoint
[Hz]/P105
P105
Setpoint
Process controller
{07}
0-10V
(10V=100%)
P105*
U
AIN
(V)/10V
±100% 16384
INT
4000
hex
16384
dec
C000
hex
-
16385
dec
4000
hex
*
s
etpoint
[Hz]/P105
P105
Torque current
limit
{11}, {12}
0-10V
(10V=100%)
P112*
U
AIN
(V)/10V
0…100% 16384 INT 4000
hex
16384
dec
/
4000
hex
* I[A]/P112
P112
Current limit
{13}, {14}
0-10V
(10V=100%)
P536*
U
AIN
(V)/10V
0…100% 16384 INT 4000
hex
16384
dec
/
4000
hex
* I[A]/P536
P536
Ramp time
{15}
0-10V
(10V=100%)
10s*
U
AIN
(V)/10V
0…200% 32767 INT 4000
hex
16384
dec
/ 10s
*
Bus setpoint/4000
hex
20s
Actual values
{Function}
Actual frequency
{01}
0-10V
(10V=100%)
P105*
U
AOut
(V)/10V
±100% 16384
INT
4000
hex
16384
dec
C000
hex
-
16385
dec
4000
hex
*
f[Hz]/P105
Speed
{02}
0-10V
(10V=100%)
P202*
U
AOut
(V)/10V
±200% 32767
INT
4000
hex
16384
dec
C000
hex
-
16385
dec
4000
hex
*
n[rpm]/P202
Current
{03}
0-10V
(10V=100%)
P203*
U
AOut
(V)/10V
±200% 32767
INT
4000
hex
16384
dec
C000
hex
-
16385
dec
4000
hex
*
f[Hz]/P105
Torque current
{04}
0-10V
(10V=100%)
P112* 100/
√
((P203)²-(P209)²)*
U
AOut
(V)/10V
±200% 32767
INT
4000
hex
16384
dec
C000
hex
-
16385
dec
4000
hex
*
I
q
[A]/(P112)*100/
√
((P203)²-(P209)²)
Master value
setpoint frequency
{19} … {21}
0-10V
(10V=100%)
P105*
U
AOut
(V)/10V
±100% 16384
INT
4000
hex
16384
dec
C000
hex
-
16385
dec
4000
hex
* f[Hz]/P105
Speed from
speed encoder
{22}
0-10V
(10V=100%)
P201/
(60/number of pole
pairs)*
U
AOut
(V)/10V
±100% 16384
INT
4000
hex
16384
dec
C000
hex
-
16385
dec
4000
hex
* n[rpm]/
P201/(60/number of
pole pairs)
Summary of Contents for SK 200E Series
Page 1: ...GB BU 0200 NORDAC SK 200E Frequency inverter manual Quick commissioning page 123...
Page 2: ...NORDAC SK 200E Manual 2 BU 0200 GB...
Page 138: ...NORDAC SK 200E Manual 138 Subject to technical alterations BU 0200 GB 5 4 6 Certificate...
Page 262: ...NORDAC SK 200E Manual 262 BU 0200 GB...
Page 263: ...10 Keyword index BU 0200 GB 263...
Page 264: ...NORDAC SK 200E Manual 264 BU 0200 GB Part No 607 2002 1310...
Page 265: ...The Nordac SK 200E is available to order from www inverterdrive com...