NORDAC SK 200E Manual
164
Subject to technical alterations BU
0200
GB
Parameter
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P400 ... P403
Output
frequency
P104
z.B. 0,0 V 2,5 V 5,0 V 10,0 V
P105
positive
P402 P403
Setpoint
voltage
Output
frequency
P104
z.B. 0,0 V 2,5 V 5,0 V 10,0 V
P105
positive
negative
P402
P403
Setpoint
voltage
P404
[-01]
[-02]
reserved
P410
Min
imum
freq
uency
a-in 1/2
(auxiliary setpoint value)
P
-400.0 ... 400.0 Hz
{ 0.0 }
The minimum frequency that can act on the setpoint via the auxiliary setpoints.
Auxiliary setpoints are all frequencies which are additionally supplied for further functions in the
FI:
Frequency
addition
Frequency
subtraction
Auxiliary setpoints via BUS
PI process controller
PI
controller
Multiplication
P411
Max
imum
freq
uency
a-in 1/2
(auxiliary setpoint value)
P
-400.0 ... 400.0 Hz
{ 50.0 }
The maximum frequency that can act on the setpoint via the auxiliary setpoints.
Auxiliary setpoints are all frequencies which are additionally delivered for further functions in the
FI:
Frequency
addition
Frequency
subtraction
Auxiliary setpoints via BUS
PI process controller
PI
controller
Multiplication
Summary of Contents for SK 200E Series
Page 1: ...GB BU 0200 NORDAC SK 200E Frequency inverter manual Quick commissioning page 123...
Page 2: ...NORDAC SK 200E Manual 2 BU 0200 GB...
Page 138: ...NORDAC SK 200E Manual 138 Subject to technical alterations BU 0200 GB 5 4 6 Certificate...
Page 262: ...NORDAC SK 200E Manual 262 BU 0200 GB...
Page 263: ...10 Keyword index BU 0200 GB 263...
Page 264: ...NORDAC SK 200E Manual 264 BU 0200 GB Part No 607 2002 1310...
Page 265: ...The Nordac SK 200E is available to order from www inverterdrive com...