6 Parameterisation
BU 0200 GB
Subject to technical alterations
179
Parameter
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P513 Telegram
timeout
(system bus)
S
-0.1 / 0.0 /
0.1 ... 100.0 s
{ 0.0 }
Monitoring of the system bus. Following receipt of a valid telegram, the next one must arrive
within the set period. Otherwise the FI reports an error and switches off with the error message
E010 >Bus Time Out<.
0.0 =
10.8/10.2 inactive
(Off)
: Monitoring is switched off.
-0.1 =
no error
: Even if the communication between the BusBox and the FI is interrupted
(e.g. 24V error, Box unplugged, etc.) the FI continues to operate unchanged.
0.1… =
10.8/10.2 active
(On)
: Monitoring is activated.
Note:
As the transfer rate of the system bus must remain at 250kBaud (Parameter (P514)), a
minimum monitoring time of 0.3 s must be set. Otherwise the FI will immediately go into error
status.
P514
CAN bus baud rate
(system bus)
S
Setting of the transfer rate (transfer speed) via the system bus interface. All bus participants
must have the same baud rate setting.
Note:
Optional modules (SK xU4-…) only operate with a transfer rate of 250kBaud. Therefore the
frequency inverter must remain at the factory setting (250kBaud).
0 =
10kBaud
1 =
20kBaud
2 =
50kBaud
3 =
100kBaud
4 =
125kBaud
5 = 250kBaud
6 =
500kBaud
7 =
1Mbaud *
0 ... 7
{ 5 }
*) Reliable operation cannot be guaranteed
P515
[-01]
...
[-03]
CAN bus address
(system bus)
S
Setting of the system bus address.
0 ... 255
dec
{ all 32
dec
}
or { all 20
hex
}
[-01] =
Slave address
,system bus reception address
[-02] =
Broadcast slave ad
d
r
ess
, system bus reception address (slave)
[-03] =
Broadcast
master address,
transmission address for system bus (master)
NOTE:
If up to four SK 200E are to be linked via the system bus, the addresses must be set as follows
Æ
FI1 = 32, FI2 = 34, FI3 = 36, FI4 = 38.
The system bus addresses should be set via the DIP switches 1/2 (Section 5.1.1).
P516
Skip frequency 1
S
P
0.0 ... 400.0 Hz
{ 0.0 }
The output frequency around the frequency value (P517) set here is masked.
This range is transmitted with the set brake and acceleration ramp; it cannot be continuously
supplied to the output. Frequencies below the absolute minimum frequency should not be set.
0.0 =
Off
: Masking frequency inactive
P517 Skip
freq
uency
area 1
S
P
0.0 ... 50.0 Hz
{ 2.0 }
Masking range for the >Masking frequency 1< P516. This frequency value is added and
subtracted from the masking frequency.
Masking frequency range 1: P516 - P517 to P516 + P517
P518
Skip frequency 2
S
P
0.0 ... 400.0 Hz
{ 0.0 }
The output frequency around the frequency value (P519) set here is masked.
This range is transmitted with the set brake and acceleration ramp; it cannot be continuously
supplied to the output. Frequencies below the absolute minimum frequency should not be set.
0.0 =
Off
: Masking frequency inactive
Summary of Contents for SK 200E Series
Page 1: ...GB BU 0200 NORDAC SK 200E Frequency inverter manual Quick commissioning page 123...
Page 2: ...NORDAC SK 200E Manual 2 BU 0200 GB...
Page 138: ...NORDAC SK 200E Manual 138 Subject to technical alterations BU 0200 GB 5 4 6 Certificate...
Page 262: ...NORDAC SK 200E Manual 262 BU 0200 GB...
Page 263: ...10 Keyword index BU 0200 GB 263...
Page 264: ...NORDAC SK 200E Manual 264 BU 0200 GB Part No 607 2002 1310...
Page 265: ...The Nordac SK 200E is available to order from www inverterdrive com...