Parameter
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P537 Pulse
disconnection
S
10 ... 200 % / 201
{ 150 }
This function prevents rapid shutdown of the FI according to the load. With the pulse switch-off
enabled, the output current is limited to the set value. This limitation is implemented by brief
switching off of individual output stage transistors, the actual output frequency remains
unchanged.
10...200% =
Limit value related to the FI current rating
201 =
Function is disabled; the FI supplies the maximum possible current.
NOTE:
The value set here can be undershot with a smaller value in P536.
For smaller output frequencies (<4.5Hz) or higher pulse frequencies (>6kHz or
8kHz, P504) the pulse switch-off by the power reduction (see Section 8.3) can be
undershot.
NOTE:
If the pulse switch-off is disabled (P537=201) and a high pulse frequency is
selected in parameter P504, the FI automatically reduces the pulse frequency
when the power limit is reached. If the load on the FI is again reduced, the pulse
frequency increases to the original value again.
P539
Check output voltage
S
P
0 ... 3
{ 0 }
This protective function monitors the output current at the U-V-W terminals and checks for
plausibility. In cases of error, the error message E016 is output.
0 = Disabled:
Monitoring is not active.
1 = Only motor phase
errors
:
The output current is measured and checked for symmetry. If
an imbalance is present, the FI switches off and outputs the error message E016.
2 = Only magnetisation
monitoring
:
At the moment the FI is switched on, the level of the
excitation current (field current) is checked. If insufficient excitation current is present,
the FI switches off with the error message E016. A motor brake is not released in this
phase.
3 = Motor phas
e
+ magnet
isation
monitoring
: as 1 and 2 combined
NOTE:
This function can also be used as an additional protective function for lifting
applications, but is not permissible on its own as protection for persons.
Summary of Contents for SK 200E Series
Page 1: ...GB BU 0200 NORDAC SK 200E Frequency inverter manual Quick commissioning page 123...
Page 2: ...NORDAC SK 200E Manual 2 BU 0200 GB...
Page 138: ...NORDAC SK 200E Manual 138 Subject to technical alterations BU 0200 GB 5 4 6 Certificate...
Page 262: ...NORDAC SK 200E Manual 262 BU 0200 GB...
Page 263: ...10 Keyword index BU 0200 GB 263...
Page 264: ...NORDAC SK 200E Manual 264 BU 0200 GB Part No 607 2002 1310...
Page 265: ...The Nordac SK 200E is available to order from www inverterdrive com...