6 Parameterisation
BU 0200 GB
Subject to technical alterations
149
Parameter
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P113 Jog
frequency
S
P
-400.0 ... 400.0 Hz
{ 0.0 }
When using the
SimpleBox or ParameterBox
to control the FI, the jog frequency is the initial
value following enabling.
Alternatively, when control is via the control terminals, the jog frequency can be activated via one
of the digital inputs.
The setting of the jog frequency can be carried out directly via this parameter or, if the FI is
enabled via the keyboard, by pressing the OK key. In this case, the actual output frequency is set
in parameter P113 and is then available for the next start.
NOTE:
Specified setpoints via the control terminals, e.g. jog frequency, fixed frequencies or
analog setpoints, are generally added with the correct sign. The set maximum
frequency (P105) cannot be exceeded and the minimum frequency (P104) cannot be
undershot.
P114
Brake delay off
(release time)
S
P
0 ... 2.50 s
{ 0.00 }
Electromagnetic brakes have a delayed reaction time during release, which depends on physical
factors. This can lead to the motor starting while the brake is still applied, which will cause the
inverter to switch off with an overcurrent report.
This release time can be taken into account in parameter P114 (Braking control).
During the adjustable release time, the FI supplies the set absolute minimum frequency (P505)
thus preventing movement against the brake.
See also the parameter >Brake reaction time< P107 (setting example).
NOTE:
If the brake release time is set to "0", then P107 is the brake release and reaction
time.
P120
[-01]
...
[-04]
Ext
ernal
Control Units
S
Array levels:
Setting values, for each array:
0 ... 2
{ 1 }
[-01] =
Bus TB (Extn. 1)
[-02] =
Analog TB (Extn.2)
(second I/O-TB)
[-03] =
Analog TB (Extn.3)
(first I/O-TB)
[-04] =
Extension 4
(reserved)
0 = Monitoring off
1 = Auto
: communications are only monitored if
an existing communication is interrupted. If
after switching on the mains a module which
was previously present is not detected, this
does not result in an error.
The monitoring only becomes active when
one of the extensions commences
communication with the FI.
2 = Monitoring
active immediately
: immediately
after being connected to the mains, the FI
commences monitoring the relevant module.
If the module is not detected after the mains
have been switched on, the FI remains in
the
state “Not on standby” for 5 seconds and
then triggers an error message.
Summary of Contents for SK 200E Series
Page 1: ...GB BU 0200 NORDAC SK 200E Frequency inverter manual Quick commissioning page 123...
Page 2: ...NORDAC SK 200E Manual 2 BU 0200 GB...
Page 138: ...NORDAC SK 200E Manual 138 Subject to technical alterations BU 0200 GB 5 4 6 Certificate...
Page 262: ...NORDAC SK 200E Manual 262 BU 0200 GB...
Page 263: ...10 Keyword index BU 0200 GB 263...
Page 264: ...NORDAC SK 200E Manual 264 BU 0200 GB Part No 607 2002 1310...
Page 265: ...The Nordac SK 200E is available to order from www inverterdrive com...