5 Commissioning
BU 0200 GB
Subject to technical alterations
125
SK
200E,
internal
view
Plug
‐
in
EEPROM
8
‐
pin
DI
P
swit
ch
5.1.2
DIP switch configuration
The DIP switches provide the possibility of carrying out commissioning without additional control units.
Additional settings are made using the potentiometer on the top of the frequency inverter.
As supplied, all DIP switches are at the “Off” position, which corresponds to control via the digital inputs
(see Section 5.1). The frequency setpoint value is adjusted via P1 and P2.
NOTE
FACTORY SETTING, AS DELIVERED!
*) As delivered, all DIP switches are in the “off” position. Control is by means of the digital
control signals (P420 [01]-[04]) and the potentiometers P1 and P2 integrated in the FI
(P400 [01]-[02]).
NOTE
For controlling the frequency inverter via In/Out bits (e.g.: AS-i, DIG In 1 - 4) typical values
are preset in the relevant parameters (P480) and (P481). (Details: Section 6)
These settings apply to both control via AS-i bits and BUS I/O bits.
No.
Bit
DIP
switch
off
Behaviour corresponding to P555, P556, P557
8
2
7
Int R
Brake
Internal brake
resistor
on
Behaviour corresponding to the brake resistor
used
off
Motor data corresponding to the rated power of
the FI in kW relative to 50Hz, fmax = 50Hz
7
2
6
60Hz*
50/60Hz-operation
on
Motor data corresponding to the rated power of
the FI in hp relative to 60Hz, fmax = 60Hz
off
VFC regulation corresponding to P211/P212
6
2
5
V/F
Regulating
process
on
V/f curve (
⇒
P211=0 and P212=0)
off
off
Corresponding to P420 [1-4] and P400 [1-2]
or P480 [1-4] and P481 [1-4]
off on
on off
5/4
2
4/3
I/O
Potentiometer
function, digital
inputs and AS
interface
on on
Further details in the next table.
(depends on the DIP3 "BUS")
off
Corresponding to P509 and P510 [1] [2]
3
2
2
BUS
Source control word
and setpoint value
on
System bus (
⇒
P509=4 and P510=4)
off
off
Corresponding to P514 and 515 [32,
250kBaud]
off
on
Address 34, 250kBaud
on
off
Address 36, 250kBaud
2/1
2
1/0
ADR
System bus
address/ baud rate
on
on
Address 38, 250kBaud
*) A changed setting is applied the next time the mains is switched on.
Existing settings in parameters P201-P209 and P105 are overwritten!
Summary of Contents for SK 200E Series
Page 1: ...GB BU 0200 NORDAC SK 200E Frequency inverter manual Quick commissioning page 123...
Page 2: ...NORDAC SK 200E Manual 2 BU 0200 GB...
Page 138: ...NORDAC SK 200E Manual 138 Subject to technical alterations BU 0200 GB 5 4 6 Certificate...
Page 262: ...NORDAC SK 200E Manual 262 BU 0200 GB...
Page 263: ...10 Keyword index BU 0200 GB 263...
Page 264: ...NORDAC SK 200E Manual 264 BU 0200 GB Part No 607 2002 1310...
Page 265: ...The Nordac SK 200E is available to order from www inverterdrive com...