NORDAC SK 200E Manual
32
Subject to technical alterations BU
0200
GB
2.4 Voltage limitation filter SK CIF
2.4.1
General information
Modules
SK CIF-323-20,
SK CIF-323-40, SK CIF-340-30 and SK CIF-340-60
are voltage limitation filters
corresponding to CSA 22.2 No. 14-5 / UL508C Section 48 for the reduction of a 5kV surge impulse (rising
flank 1,2µs / falling flank 50µs) to a maximum of 300% of the amplitude of the rated voltage (230Vac for
SK CIF 323-20/40 and 3x400Vac/460Vac/480Vac/500Vac for SK CIF-340-30/60).
ATTENTION
The modules SK CIF-323-x0 may
only be used in combination with a suitable mains choke
(L
min
= 3 x 0,73 mH) (see connection plan).
With SK CIF-340-x0 modules, the use of a mains choke is not essential, but is recommended.
Note
With the use of a mains choke, the effective input currents of the frequency inverter are reduced to
approximately the values of the output currents. Several frequency inverters may be connected to a
choke - filter combination. In this case, the sum of the input currents must not exceed the rated
current of the filter.
2.4.2
Type code
SK CIF-323-20
Rated current:
20 = 20A
, 30 = 30A, 40 = 40A, 60 = 60A
Mains voltage:
x23 = 230V
, x40 = 400V
Number of mains phases: 3 = 3-phase
Device series:
CIF = voltage limitation filter (CSA - Filter)
Summary of Contents for SK 200E Series
Page 1: ...GB BU 0200 NORDAC SK 200E Frequency inverter manual Quick commissioning page 123...
Page 2: ...NORDAC SK 200E Manual 2 BU 0200 GB...
Page 138: ...NORDAC SK 200E Manual 138 Subject to technical alterations BU 0200 GB 5 4 6 Certificate...
Page 262: ...NORDAC SK 200E Manual 262 BU 0200 GB...
Page 263: ...10 Keyword index BU 0200 GB 263...
Page 264: ...NORDAC SK 200E Manual 264 BU 0200 GB Part No 607 2002 1310...
Page 265: ...The Nordac SK 200E is available to order from www inverterdrive com...