Subject to technical alterations BU
0200
GB
Display in the
SimpleBox
Group
Details in
P700[-01] /
P701
Error
Text in the Parameter Box
Cause
Remedy
15.0 Wrong
s
oft
ware version
Check software version
15.1
P
watchdog
15.2
P
stack overflow
15.3
P
stack underflow
15.4 Undefined
P
opcode
15.5
P
Protected Instruct
15.6
P
illegal WordAccess
15.7
P
illegal InstAccess
E015
15.8
P
Prog
ram
memory
error
System error in program execution, triggered by EMC
interference.
Please comply with wiring guidelines in Section 2.5.
Use additional external mains filter. (Section 9.3 / 9.4 EMC)
FI must be very well earthed.
16.0
Motor phase error
A motor phase is not connected.
Check P539
Check motor connections
E016
16.1 Magn
etisation
Current Watch
Required excitation current not achieved at moment of
switch-on.
Check P539
Check motor connections
E018
18.0
Safety circuit
The
safe pulse block
was triggered while the frequency
inverter was being enabled.
Only available in SK 215E and SK 235E. Details in Manual
BU 0230 (
www.nord.com
).
19.0 Parameter
ident
ification
E019
19.1
Motor
star
-/
delta
circuit
incorrect
Automatic identification of the connected motor was
unsuccessful
Check motor connections
Check preset motor data (P201 … P209)
Summary of Contents for SK 200E Series
Page 1: ...GB BU 0200 NORDAC SK 200E Frequency inverter manual Quick commissioning page 123...
Page 2: ...NORDAC SK 200E Manual 2 BU 0200 GB...
Page 138: ...NORDAC SK 200E Manual 138 Subject to technical alterations BU 0200 GB 5 4 6 Certificate...
Page 262: ...NORDAC SK 200E Manual 262 BU 0200 GB...
Page 263: ...10 Keyword index BU 0200 GB 263...
Page 264: ...NORDAC SK 200E Manual 264 BU 0200 GB Part No 607 2002 1310...
Page 265: ...The Nordac SK 200E is available to order from www inverterdrive com...