6 Parameterisation
BU 0200 GB
Subject to technical alterations
183
Parameter
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P540
Mode phase sequence
S
P
0 ... 7
{ 0 }
For safety reasons this parameter can be used to prevent a rotation direction reversal and
therefore the incorrect rotation direction.
This function does not operate if the position control is active (P600
≠
0).
0 = No
rotation direction
limitation
1 = Disable phase seq
uence
key,
rotation direction change key
of the SimpleBox is
locked
2 = To the right only
*, only right-hand field rotation direction is possible. The selection of
the "incorrect" rotation direction leads to the output of the minimum frequency P104
with the field of rotation R.
3 = To the left only
*, only a left-hand field rotation direction is possible. The selection of the
"incorrect" rotation direction leads to the output of the minimum frequency P104 with
the field of rotation L.
4 = Enabl
e
direct
ion
only
, rotation direction is only possible according to the enable signal,
otherwise 0Hz is output.
5 = Right Orient. Contr.
(only right-hand running monitored)
*, only a right-hand field
rotation is possible. The selection of the "incorrect" rotation direction leads to a switch-
off (control lock) of the FI. If necessary, care should be taken that the setpoint (>f
min
) is
sufficiently high.
6 = Right Orient. Contr.
(only left-hand running monitored)
*, only a left field rotation is
possible. The selection of the "incorrect" rotation direction leads to a switch-off (control
lock) of the FI. If necessary, care should be taken that the setpoint (>f
min
) is sufficiently
high.
7 =
Only
enab
led
direct
ion
contr
olled
, rotation is only possible in the direction of the
enable signal, otherwise the FI is switched off.
*) Applies for control via keyboard and control terminals.
P541 Set
digital output
S
This function provides the opportunity to control the relay and the digital outputs independently
of the frequency inverter status. To do this, the relevant output must be set to the function
"External control".
This function can either be used manually or in combination with a bus control.
Bit 0 =
Digital output 1
Bit 1 =
Bus/AS-i Out Bit 0
Bit 2 =
Bus/AS-i Out Bit 1
Bit 3 =
Bus/AS-i Out Bit 2
Bit 4 =
Bus/AS-i Out Bit 3
Bit 5 =
Bus/An
alog
/Dig
ital
Out Bit 4
Bit 6 =
Bus/An
alog
/Dig
ital
Out Bit 5
Bit 7 =
Bus dig
ital
out
put
7
Bit 8 =
Bus dig
ital
out
put
8
Bit 8
Bits 7 -4
Bits 3 -0
Min. value
0
0
0000
0
0000
0
Binary
hex
Max. value
1
1
1111
F
1111
F
Binary
hex
000 ... 1FF
(hex)
{ 000 }
Setting of the value via …
BUS:
The corresponding hex value is written into the parameter, thereby setting
the relay or digital outputs.
SimpleBox:
The hexadecimal code is entered directly if the SimpleBox is used.
ParameterBox:
Each individual output can be separately called up in plain text and
activated.
Summary of Contents for SK 200E Series
Page 1: ...GB BU 0200 NORDAC SK 200E Frequency inverter manual Quick commissioning page 123...
Page 2: ...NORDAC SK 200E Manual 2 BU 0200 GB...
Page 138: ...NORDAC SK 200E Manual 138 Subject to technical alterations BU 0200 GB 5 4 6 Certificate...
Page 262: ...NORDAC SK 200E Manual 262 BU 0200 GB...
Page 263: ...10 Keyword index BU 0200 GB 263...
Page 264: ...NORDAC SK 200E Manual 264 BU 0200 GB Part No 607 2002 1310...
Page 265: ...The Nordac SK 200E is available to order from www inverterdrive com...