6 Parameterisation
BU 0200 GB
Subject to technical alterations
147
Parameter
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P108 Disconnection
mode
S
P
0 ... 13
{ 1 }
This parameter determines the manner in which the output frequency is reduced after "Blocking"
(controller enable
Æ
Low).
0 = Voltage disable:
The output signal is switched off immediately. The FI no longer supplies
an output frequency. In this case, the motor is braked only by mechanical friction.
Immediately switching the FI on again can lead to an error message.
1 = Ramp down:
The current output frequency is reduced in proportion to the remaining
deceleration time, from P103/P105.
2 = Delayed ramping:
as with ramp, however for generational operation the brake ramp is
extended, or for static operation the output frequency is increased. Under certain
conditions, this function can prevent overload switch off or reduce brake resistance
power dissipation.
NOTE:
This function must not be programmed if defined deceleration is required, e.g.
with lifting mechanisms.
3 = Instant DC braking:
The FI switches to the preselected DC current (P109) immediately.
This DC current is supplied for the remaining proportion of the >DC brake time< (P110).
Depending on the relationship of the actual output frequency to the max. frequency
(P105), the >DC braking time< is shortened. The time taken for the motor to stop
depends on the application. This depends on the inertia of the load, the friction and the
DC current which is set (P109).
With this type of braking, no energy is fed back to the FI. Heat losses occur primarily in
the rotor of the motor.
4 = Const
ant
brake distance:
The brake ramp starts after a delay if the equipment is not
being driven at the maximum output frequency (P105). This results in an approximately
similar stopping distance for different frequencies.
NOTE:
This function cannot be used as a positioning function. This function should not
be combined with ramp smoothing (P106).
5 = Combi
ned
braking:
Dependent on the actual link voltage (VDC), a high frequency
voltage is switched to the basic frequency (linear characteristic curves only, P211 = 0
and P212 = 0). The deceleration time is retained where possible (P103).
Æ
additional
motor warming!
6 = Quadratic ramp:
The brake ramp does not follow a linear path, but rather a decreasing
quadratic one.
7 = Quad
ratic
ramp with delay:
Combination of functions 2 and 6
8 = Quad
ratic
ramp w
ith
combined
braking:
Combination of functions 5 and 6
9 = Constant acc
eleratio
n
power
:
Only applies in field weakening range! The drive is further
accelerated or braked with a constant electrical power. The ramp depends on the load.
10 = Distance calculator:
Constant distance between actual frequency / speed and the set
minimum output frequency (P104).
11 = Constant
acc
eleratio
n
power with
delay:
Combination of functions 2 and 9.
12 = Constant
acc
eleratio
n
power
Mode3:
as 11 with additional brake chopper relief
13 = Switch-off delay
Summary of Contents for SK 200E Series
Page 1: ...GB BU 0200 NORDAC SK 200E Frequency inverter manual Quick commissioning page 123...
Page 2: ...NORDAC SK 200E Manual 2 BU 0200 GB...
Page 138: ...NORDAC SK 200E Manual 138 Subject to technical alterations BU 0200 GB 5 4 6 Certificate...
Page 262: ...NORDAC SK 200E Manual 262 BU 0200 GB...
Page 263: ...10 Keyword index BU 0200 GB 263...
Page 264: ...NORDAC SK 200E Manual 264 BU 0200 GB Part No 607 2002 1310...
Page 265: ...The Nordac SK 200E is available to order from www inverterdrive com...