Parameter
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P419
[-01]
[-02]
Analog output scal.
(Standardisation, analog output 1)
S
P
-500 ... 500 %
{ all 100 }
[-01] =
First IOE,
AOUT of the first I/O extension (SK xU4-IOE)
[-02] =
Second IOE,
AOUT of the second I/O extension (SK xU4-IOE)
... only with
SK CU4-IOE or
SK TU4-IOE
Using this parameter an adjustment can be made to the analog output for the selected operating
zone. The maximum analog output (10V) corresponds to the standardisation value of the
appropriate selection.
If therefore, at a constant working point, this parameter is raised from 100% to 200%, the analog
output voltage is halved. 10 Volt output signal then corresponds to twice the nominal value.
For negative values the logic is reversed. A setpoint value of 0% will then produce 10V at the
output and -100% will produce 0V.
P420
[-01]
...
[-04]
Digital inputs
0 ... 72
{ [-01]= 1 }
{ [-02] = 2 }
{ [-03] = 4 }
{ [-04] = 5 }
In the SK 200E, up to 4 freely programmable digital inputs are available. The only restriction is
with the versions SK 215E and SK 235E. Here, the fourth digital input is always the input for the
function “Safe Stop”.
[-01] = Digital input 1
(DIN1)
, Enable right
as factory setting,
control terminal 21
[-02] = Digital input 2
(DIN2)
, Enable left
as factory setting,
control terminal 22
[-03] = Digital input 3
(DIN3)
, Fixed frequency 1
(P465 [-01]) as factory setting,
control terminal 23
[-04] = Digital input 4
(DIN4)
, Fixed frequency 2
(P465 [-02]) as factory setting, not with SK
215/235E
Æ
"Safe Stop", control terminal 24
Various functions can be programmed. These can be seen in the following table.
When using DIN2 and DIN3 as rotary encoder evaluation, it is essential to set the functions of the
digital inputs DIN2 and DIN3 (Parameter (P420 [-02, -03])) to “No Function”. (For using the DIP-
switches of the frequency inverter for parametrisation, please lock at section 5.1.2 .)
The additional digital inputs of the I/O- extensions (SK xU4-IOE) are administered via the
parameter "Bus I/O In Bit (4…7)“ - (P480 [-05] … [-08]) for the first I/O extension, and via the
parameter "Bus I/O In Bit (0…3)" - (P480 [-01] … [-04]) for the second I/O extension.
List of the possible functions of the digital inputs P420 [01]... [-04]
Value Function
Description
Signal
00
No function
Input switched off.
---
01
Enabled right
The FI delivers an output signal with the rotation field right if a
positive setpoint is present. 0
→
2 Flank (P428 = 0)
High
02
Enable left
The FI delivers an output signal with the rotation field left if a
positive setpoint is present. 0
→
2 Flank (P428 = 0)
High
If the drive is to start up automatically when the mains is switched on (P428 = 1) a permanent High level for
enabling must be provided (supply control terminal 21 with 24V).
If the functions "Enable right" and "Enable left" are actuated simultaneously, the FI is blocked.
...continued on the next page
Summary of Contents for SK 200E Series
Page 1: ...GB BU 0200 NORDAC SK 200E Frequency inverter manual Quick commissioning page 123...
Page 2: ...NORDAC SK 200E Manual 2 BU 0200 GB...
Page 138: ...NORDAC SK 200E Manual 138 Subject to technical alterations BU 0200 GB 5 4 6 Certificate...
Page 262: ...NORDAC SK 200E Manual 262 BU 0200 GB...
Page 263: ...10 Keyword index BU 0200 GB 263...
Page 264: ...NORDAC SK 200E Manual 264 BU 0200 GB Part No 607 2002 1310...
Page 265: ...The Nordac SK 200E is available to order from www inverterdrive com...