Parameter
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P552
[-01]
[-02]
CAN Master cycle
time
(system bus)
S
In this parameter, the cycle time for the system bus master mode and the CAN open encoder is
set (see P503/514/515):
[01] = CAN Master function
, cycle time for system bus master functions
[02] = CANopen abs
olute
encoder
, cycle time for system bus absolute encoder
With the setting
0 = “Auto”
the default value (see table) is used.
According to the Baud rate set, there are different minimum values for the actual cycle time:
Baud rate
Minimum value tZ
Default System Bus Master
Default System Bus Abs.
10kBaud 10ms
50ms
20ms
20kBaud 10ms
25ms
20ms
50kBaud 5ms
10ms
10ms
100kBaud 2ms
5ms
5ms
125kBaud 2ms
5ms
5ms
250kBaud 1ms
5ms
2ms
500kBaud 1ms
5ms
2ms
0.0 / 0.1 … 100.0 ms
{ all 0.0 }
1000kBaud: 1ms
5ms
2ms
P555 P
Chopper
Limit
S
5 ... 100 %
[ 100 ]
A power limit for the brake resistor can be programmed with this parameter. The switch-on time
(modulation level) for the brake chopper can only increase to the maximum specified limit.
The result would be an overvoltage switch-off of the FI.
The correct percentage value is calculated as follows:
2
max
max
*
[%]
U
P
R
k
BR
=
R =Brake resistor resistance
P
maxBR
= short-term peak power of the brake resistor
U
max
= chopper switching wave from the FI
1~
115/230V
⇒
440V=
3~ 230V~
⇒
500V=
3~ 400V~
⇒
1000V=
NOTE:
With the use of the internal brake resistor SK BRI4-… a suitable limit must be set.
However, the activation of the limit via the DIP switch (Section 5.1.1), DIP8 = “On”
is recommended.
P556 Braking
resistor
S
20 ... 400
Ω
{ 120 }
Value of the brake resistance for the calculation of the maximum brake power to protect the
resistor.
Once the maximum continuous output (P557) including overload (200% for 60s) is reached, an
I
2
t limit error (E003.1) is triggered. Further details in P737.
P557
Brake resistor type
S
0.00 ... 20.00 kW
{ 0.00 }
Continuous power (nominal power) of the resistor, to display the actual utilisation in P737. For a
correctly calculated value, the correct value must be entered into P556 and P557.
0.00 =
Off,
monitoring disabled
Summary of Contents for SK 200E Series
Page 1: ...GB BU 0200 NORDAC SK 200E Frequency inverter manual Quick commissioning page 123...
Page 2: ...NORDAC SK 200E Manual 2 BU 0200 GB...
Page 138: ...NORDAC SK 200E Manual 138 Subject to technical alterations BU 0200 GB 5 4 6 Certificate...
Page 262: ...NORDAC SK 200E Manual 262 BU 0200 GB...
Page 263: ...10 Keyword index BU 0200 GB 263...
Page 264: ...NORDAC SK 200E Manual 264 BU 0200 GB Part No 607 2002 1310...
Page 265: ...The Nordac SK 200E is available to order from www inverterdrive com...