6 Parameterisation
BU 0200 GB
Subject to technical alterations
155
Parameter
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P220 Para
meter
identification
P
... up to 240s
{ 0 }
The motor data is automatically determined by the FI with this parameter. In most cases this
leads to considerably better drive characteristics, as DC asynchronous motors are subject to
manufacturing tolerances which are not documented on the rating plate.
The identification of all parameters takes some time. Do not switch off the mains voltage during
this time. The identification can only be carried out in an “operative” condition. This must be
particularly taken into account in BUS operation.
If unfavourable operating characteristics result, select a suitable motor in P200 or set the
parameters P201 … P208 manually.
0 = No identification
1 = Identification RS:
only the stator resistance (display in P208) is determined by multiple
measurements.
2 = Identification motor:
all motor parameters (P202, P203, P206, P208, P209) are
determined.
Procedure:
a) The identification should be made with the motor cold. Warming up of the motor during
operation is automatically taken into account.
b) The FI must be in an “operative condition” For bus operation, the bus must be operating
without error. The FI must not be in a state of switch-on block.
c) The motor power may only be one power level greater or 3 power levels lower than the
nominal power of the FI.
d) The motor data should be set according to the rating plate or P200. However, at least
the nominal frequency (P201), the nominal speed (P202), the voltage (P204), the power
(P205) and the motor circuit (P207) should be known.
e) If the identification cannot be concluded successfully, the error message E019 is
generated. See also Section 6, Error messages.
f) Reliable identification can be made with motor cables up 20m in length.
NOTE:
After identification of parameters, P220 is again = 0.
Care must be taken that the connection to the motor is not interrupted during the
entire measuring process.
Summary of Contents for SK 200E Series
Page 1: ...GB BU 0200 NORDAC SK 200E Frequency inverter manual Quick commissioning page 123...
Page 2: ...NORDAC SK 200E Manual 2 BU 0200 GB...
Page 138: ...NORDAC SK 200E Manual 138 Subject to technical alterations BU 0200 GB 5 4 6 Certificate...
Page 262: ...NORDAC SK 200E Manual 262 BU 0200 GB...
Page 263: ...10 Keyword index BU 0200 GB 263...
Page 264: ...NORDAC SK 200E Manual 264 BU 0200 GB Part No 607 2002 1310...
Page 265: ...The Nordac SK 200E is available to order from www inverterdrive com...