6 Parameterisation
BU 0200 GB
Subject to technical alterations
143
Parameter
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P002 Display
Factor
S
0.01 ... 999.99
{ 1.00 }
The selected operating value in parameter P001 >Select of display< is multiplied with the
scaling factor in P000 and displayed in >Operating parameter display<.
It is therefore possible to display system-specific operating such as e.g. the throughput quantity
P003 Supervisor
code
0 ... 9999
{ 1 }
0 =
All parameters are visible except for the Supervisor parameters and the group P3xx/
P6xx
1 =
All parameters are visible except for the group P3xx and P6xx.
2 =
All parameters are visible except for the group P6xx.
3 =
All parameters are visible.
4 =
... 9999, (except 65) only parameters P001 and P003 are visible.