NORDAC SK 200E Manual
160
Subject to technical alterations BU
0200
GB
Parameter
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
10 = Cur
rent
freq
uency,
sup
e
rv
i
s
e
d by PI
*,
11 = Torque
current
limit
ation (limiting)
, depends on parameter (P112), this value
corresponds to 100% of the setpoint value. Attainment of the set limiting value causes a
reduction of the output frequency at the limit of the torque current.
12 = Torqu
e
curr
ent
limit
ation (switch-
off
)
, depends on parameter (P112), this value
corresponds to 100% of the setpoint value. The attainment of this set limiting value
causes switch-off with error code E12.3.
13 = Current limit
(limiting)
, depends on parameter (P536). This value corresponds to 100%
of the setpoint value. The attainment of the set limiting value causes a reduction of the
output voltage in order to limit the output current.
14 = Current
limit
(switch-
off
)
, depends on parameter (P536), this value corresponds to
100% of the setpoint value. The attainment of this set limiting value causes switch-off
with error code E12.4.
15 = Ramp time
, is a typical setting value for the function of the potentiometers P1 or P2
(P400 [01] or [02]), which are integrated in the cover of the FI (Section 5.1.3).
Standardisation: T_Ramp time= 100Hz*U[V]/10V (U=voltage potentiometer (P1 or P2))
16 = Pre-tension Torque
, function which enables a value for the anticipated torque
requirement to be entered in the controller (interference factor switching). This function
can be used to improve the load take-up of lift equipment with separate load detection.
17 = Multiplication
, the setpoint is multiplied with the specified analog value. The analog
value adjusted to 100% then corresponds to a multiplication factor of 1.
18 = Curve control
(Curve travel calculator)
, via the external analog input (P400 [-03] or
P400 [-04]) or via the BUS (P546 [-01 .. -03]) the master receives the actual speed from
the slave. From its own speed, the slave speed and the guide speed, the master
calculates the actual setpoint speed, so that neither of the two drives travels faster than
the guide speed in the curve.
19 = Servo mode torque
, in servo mode, the motor torque can be set or limited using this
function.
25 = Ratio gearing
(Gearing transformation factor)
, is a multiplier which takes into account
a variable transformation of the setpoint value. E.g.: Setting of the transformation
between the master and the slave by means of a potentiometer.
30 = Motor temperature
: enables measurement of the motor temperature with a
KTY-84 - temperature sensor (Details in Section 5.3)
33 = Set
point
val
ue
torque
p
rocess
controller
: for the even distribution of torques to the
coupled drive units (e.g.: synchronised roller drive). This function is also possible with
the use of ISD control.
*) For further details of the PI and process controller, please refer to Section 9.2.
**) The limits of these values are formed by the parameters >minimum frequency auxiliary
setpoint values< (P410) and the parameter >maximum frequency auxiliary setpoint values<
(P411), whereby the limits defined by (P104) and (P105) cannot be undershot or overshot.
Summary of Contents for SK 200E Series
Page 1: ...GB BU 0200 NORDAC SK 200E Frequency inverter manual Quick commissioning page 123...
Page 2: ...NORDAC SK 200E Manual 2 BU 0200 GB...
Page 138: ...NORDAC SK 200E Manual 138 Subject to technical alterations BU 0200 GB 5 4 6 Certificate...
Page 262: ...NORDAC SK 200E Manual 262 BU 0200 GB...
Page 263: ...10 Keyword index BU 0200 GB 263...
Page 264: ...NORDAC SK 200E Manual 264 BU 0200 GB Part No 607 2002 1310...
Page 265: ...The Nordac SK 200E is available to order from www inverterdrive com...