NORDAC SK 200E Manual
176
Subject to technical alterations BU
0200
GB
6.1.6
Additional parameters
Parameter
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P501
Inverter
name
A…Z
(char)
{ 0 }
Free input of a designation (name) for the device (max. 20 characters). With the the frequency
inverter can be uniquely identified for processing with NordCon software or within a network.
P502
[-01]
...
[-03]
Value master function
S
P
Selection of up to 3 master values:
[-01] = Master value 1
[-02] = Master value 2
[-03] = Master value 3
Selection of possible setting values for master values:
0 ... 21
{ all 0 }
0 =
Off
1 =
Actual frequency
2 =
Actual speed
3 =
Current
4 =
Torque current
5 =
Status Digital IO
6 =
... 7 reserved
8 =
Setpoint frequency
9 =
Error coder
10 =
... 11 reserved
12 =
Bus IO Out Bits 0-7
13 =
... 16 reserved
17 =
Value
of
analog in
put
1
(first IOE)
18 =
Value
of
analog in
put
2
(first IOE)
19 =
Setpoint
freq
uency
master
value
20 =
Set
point
freq
uency
after ramp
,
master
value
21 =
Act
ual
freq
uency
w
ith
o
ut
slip, master
value
22 =
Speed encoder
P503 Leading
funct
ion
output
S
Activation of output of the master value onto the system bus (master functionality).
Specification of the communication modes on the system bus for ParameterBox and Nord Con.
The definition of the master value or values is carried out in parameter P502.
0 ... 3
{ 0 }
0 = Off
No
control word and master value
output.
If
no BUS option (e.g. SK xU4-IOE)
is connected to the system bus, only
the device directly connected to the
ParameterBox or Nord Con is visible.
1 = CANopen (system bus)
Control word
and master values are
transferred to the system bus.
If
no bus option (e.g. SK xU4-IOE) is
connected to the system bus, only
the device directly connected to the
ParameterBox or Nord Con is visible.
2 = System bus active
No
control word and master value
output.
All
FIs connected to the system bus
are visible in the ParameterBox or
Nord Con, even if no bus option is
connected. Prerequisite: all FIs must
be set to this mode.
3 = C Syst
em
bus act
ive
Control word
and master values are
transferred to the system bus.
All
FIs connected to the system bus
are visible in the PameterBox or Nord
Con, even if no bus option is
connected. Prerequisite: all other FIs
must be set to mode { 2 } "System bus
active"
Summary of Contents for SK 200E Series
Page 1: ...GB BU 0200 NORDAC SK 200E Frequency inverter manual Quick commissioning page 123...
Page 2: ...NORDAC SK 200E Manual 2 BU 0200 GB...
Page 138: ...NORDAC SK 200E Manual 138 Subject to technical alterations BU 0200 GB 5 4 6 Certificate...
Page 262: ...NORDAC SK 200E Manual 262 BU 0200 GB...
Page 263: ...10 Keyword index BU 0200 GB 263...
Page 264: ...NORDAC SK 200E Manual 264 BU 0200 GB Part No 607 2002 1310...
Page 265: ...The Nordac SK 200E is available to order from www inverterdrive com...