NORDAC SK 200E Manual
66
Subject to technical alterations BU
0200
GB
Details of the control connections
Terminal/
Name
Function
Data
Description / wiring suggestion
Parameter
44 24V
24V supply
-
40 GND
Reference potential
-
44 24V
24V supply
-
40 GND
Reference potential
24VDC ±10%
max. 420mA (total)
integrated
short-circuit monitoring,
limited overtemperature
and overload monitoring
Supply voltage (output) for the
supply of an SK 200E or other
module with 24V.
Can also be used as an input (in
this case, do not connect L1 and
L2), if the module is only to be
used as a voltage or frequency
converter (for the connection of a
potentiometer).
-
11 +10V
10V
reference voltage
10V ± 0.2V
Max.
load 5mA
-
14 AIN+
Analog input
positive
0 … 10V,
Resolution: 8Bit
Accuracy: 0,2V
-
12 0V
GND analog
Analog Ground
Reference potential for
analog signals
For connection of potentiometer
5 - 10k
Ω
.
A 500
Ω
burden resistor for the
evaluation of 0/4 - 20mA signals is
contained in the enclosed bag.
-
B1 FOUT
Frequency output
SPS compatible in
compliance with
EN61131-2
Low: 0V, High: 24V
Pulse frequency:
~ 1 - 32kHz
Impulses for evaluation via the
digital input function P420 [02]/[03]
= 26/27 and the analog meaning in
P400 [-06]/[-07].
P420
P400
40
Reference potential
-
Potential separation
-
L1
Mains connection
1. Phase
-
-
L2
Mains connection
2. Phase
-
Mains connection, 100 - 240V or
380 - 500V, depending on the
module
-
PE PE,
Earth
-
PE
PE, Earth
As required, does not need to be
connected.
-
Summary of Contents for SK 200E Series
Page 1: ...GB BU 0200 NORDAC SK 200E Frequency inverter manual Quick commissioning page 123...
Page 2: ...NORDAC SK 200E Manual 2 BU 0200 GB...
Page 138: ...NORDAC SK 200E Manual 138 Subject to technical alterations BU 0200 GB 5 4 6 Certificate...
Page 262: ...NORDAC SK 200E Manual 262 BU 0200 GB...
Page 263: ...10 Keyword index BU 0200 GB 263...
Page 264: ...NORDAC SK 200E Manual 264 BU 0200 GB Part No 607 2002 1310...
Page 265: ...The Nordac SK 200E is available to order from www inverterdrive com...