6 Parameterisation
BU 0200 GB
Subject to technical alterations
193
Parameter
Setting value / Description / Note
Device
Supervisor
Parameter
set
P730 Field
0 ... 250 %
Displays the actual field in the motor as calculated by the inverter. Basis for calculation is the
motor data P201...P209 ... .
P731 Parameter
set
Shows the actual operating parameter set.
0 ... 3
0 =
Parameter set 1
1 =
Parameter set 2
2 =
Parameter set 3
3 =
Parameter set 4
P732
Phase U current
S
0.0 ... 999.9 A
Displays the actual U phase current.
NOTE:
This value can deviate from the value in P719, due to the measurement procedure
used, even with symmetrical output currents.
P733
Phase V current
S
0.0 ... 999.9 A
Displays the actual V phase current.
NOTE:
This value can deviate from the value in P719, due to the measurement procedure
used, even with symmetrical output currents.
P734
Phase W current
S
0.0 ... 999.9 A
Displays the actual W phase current.
NOTE:
This value can deviate from the value in P719, due to the measurement procedure
used, even with symmetrical output currents.
P735 Speed
encoder
S
-9999 ... 9999 rpm
Displays the actual rotation speed supplied by the incremental encoder. For this, P301 must be
correctly set.
P736
D.c. link voltage
0 ... 1000 V DC
Displays the actual link voltage.
P737
Usage rate brake res
istor
0 ... 1000 %
This parameter provides information about the actual degree of modulation of the brake
chopper or the current utilisation of the braking resistor in generator mode.
If parameters P556 and P557 are correctly set, the utilisation related to P557, the resistor
power, is displayed.
If only P556 is correctly set (P557=0), the degree of modulation of the brake chopper is
displayed. Here, 100 means that the brake resistor is fully switched. On the other hand, 0
means that the brake chopper is not active at present.
If P556 = 0 and P557 = 0, this parameter also provides information about the degree of
modulation of the brake chopper in the FI.
P738
[-01]
[-02]
Usage rate motor
0 ... 1000 %
Shows the actual motor load. Basis for calculation is the motor data P203. The actual recorded
current is related to the nominal motor current.
[-01] = related to I
N
(P203) of the motor
[-02] = related
to
I
2
t control
(P535)
Summary of Contents for SK 200E Series
Page 1: ...GB BU 0200 NORDAC SK 200E Frequency inverter manual Quick commissioning page 123...
Page 2: ...NORDAC SK 200E Manual 2 BU 0200 GB...
Page 138: ...NORDAC SK 200E Manual 138 Subject to technical alterations BU 0200 GB 5 4 6 Certificate...
Page 262: ...NORDAC SK 200E Manual 262 BU 0200 GB...
Page 263: ...10 Keyword index BU 0200 GB 263...
Page 264: ...NORDAC SK 200E Manual 264 BU 0200 GB Part No 607 2002 1310...
Page 265: ...The Nordac SK 200E is available to order from www inverterdrive com...