6 Parameterisation
BU 0200 GB
Subject to technical alterations
171
Parameter
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P434
[-01]
[-02]
Digital output function
[-01] =
Digital output 1,
Digital output of the frequency inverter
[-02] =
reserved
Control terminals 1/40 (Section 2.8.2):
The settings 3 to 5 and 11 work with 10% hysteresis,
i.e. the relay contact closes (function 11 does not deliver) on reaching the limiting value 24V and
switches this off again if a 10% lower value is undershot (function 11 on again).
This behaviour can be inverted with a negative value in P435.
Setting / Function
Output ...
for limiting value
or function
(see also P435)
0 = No function
Low
1 = External brake
, to control an external 24V brake relay (max. 200mA).
The relay switches at a programmed absolute minimum frequency
(P505).
For typical brakes a setpoint delay of 0.2-0.3sec should be
programmed (see also P107/P114).
A typical motor brake (105-180-205V) can be connected directly via
the control terminals 79 MB+/80 MB- (Section 2.8.2).
High
2 = Inverter is working
, the output indicates voltage at the FI output
(U -
V - W)
.
High
3 = Current limit
, based on the setting of the motor rated current in (P203).
This value can be adjusted with the standardisation (P435).
High
4 = Torque current limit
, based on motor data settings in P203 and P206.
Signals a corresponding torque load on the motor. This value can be
adjusted with the standardisation (P435).
High
5 = Frequency limit
, based on motor nominal frequency setting in P201.
This value can be adjusted with the standardisation (P435).
High
6 = Level with setpoint
(Setpoint reached)
, indicates that the FI has
completed the frequency increase or decrease. Setpoint frequency =
actual frequency! From a difference of 1 Hz
Æ
Setpoint value not
achieved – signal Low.
High
7 = Fault
, general error message, error is active or not yet acknowledged.
Æ
Error – Low (Ready – High)
Low
8 = Warning
: general warning, a limit value was reached that could lead to
a later shutdown of the FI.
Low
9 = Overcurrent warning
: At least 130% of the nominal FI current was
supplied for 30 seconds.
Low
10 = Mot
or
overtemp
erature
warning
: The motor temperature is evaluated.
Æ
Motor is too hot. Warning occurs immediately, overheating switch-
off after 2 seconds.
Low
11 = Torque current limit
/Current limit
active warning
:
The limiting value
in P112 or P536 has been reached. A negative value in P435 inverts
the reaction. Hysteresis = 10%.
Low
12 = Value of P541
– external control
, the output can be controlled with
parameter P541 (Bit 0) independently of the actual operating status of
the FI.
High
13 = Torq
ue
curr
ent
limit gen
erator /Generator torque limit
active
:
Limit value in P112 has been reached in the generator range.
Hysteresis = 10%.
High
0 ... 39
{ 7 }
18 = Inverter ready
: The FI is in standby state. After being enabled it gives
an output signal.
High
Summary of Contents for SK 200E Series
Page 1: ...GB BU 0200 NORDAC SK 200E Frequency inverter manual Quick commissioning page 123...
Page 2: ...NORDAC SK 200E Manual 2 BU 0200 GB...
Page 138: ...NORDAC SK 200E Manual 138 Subject to technical alterations BU 0200 GB 5 4 6 Certificate...
Page 262: ...NORDAC SK 200E Manual 262 BU 0200 GB...
Page 263: ...10 Keyword index BU 0200 GB 263...
Page 264: ...NORDAC SK 200E Manual 264 BU 0200 GB Part No 607 2002 1310...
Page 265: ...The Nordac SK 200E is available to order from www inverterdrive com...