4 Display and control
BU 0200 GB
Subject to technical alterations
117
4.1.3
ParameterBox parameters
The following main functions are assigned to the menu groups
:
Menu group
No.
Master function
Display (P10xx):
Selection of operating values and display layout
Parameterisation (P11xx):
Programming of the connected inverter and all storage media
Parameter management (P12xx):
Copying and storage of complete parameter sets from storage media and
inverters
Options (P14xx):
Setting the ParameterBox functions and all automatic processes
Display
Parameter
Setting value / Description / Note
P1001
Bus scan
A bus scan is initiated with this parameter. During this process a progress indicator is
shown in the display.
After a bus scan, the parameter is "Off".
Depending on the result of this process, the ParameterBox goes into the "ONLINE" or
"OFFLINE" operating mode.
P1002
FI selection
Selection of the current item to be parameterised/controlled.
The display and further operating actions refer to the item selected. In the inverter selection
list, only those devices detected during the bus scan are shown. The current object appears
in the status line.
Value range: FI, S1 ... S5
P1003
Display mode
Selection of the operating values of the ParameterBox (Selection value(s) in (P1004))
Standard:
Any 3 values next to each other
List:
Any 3 values listed with units
Large display:
1 value (any) with unit
ControlBox:
1 (any) value without unit (Selection value in (P001) of the FI)
P1004
Values for display
Selection of a display value for the actual value display of the ParameterBox.
(See also
BU0040)
The value selected is placed in the first position of an internal list for the display value and
is then also used in the Large Display mode.
Possible actual values for the display:
Actual frequency Voltage
Current
Speed of rotation Torque current
Setpoint frequency
DC link voltage
Bus actual value1, non-standardised
P1005
Standardisation factor
The first value in the list displayed is scaled using the standardisation factor. If this
standardisation factor varies from a value of 1.00, then the units of the scaled value are
hidden in the display.
Value range: -327.67 to +327.67; resolution 0.01
Parameterisation
Parameter
Setting value / Description / Note
P1101
Object selection
Selection of the object to be parameterised.
The ongoing parameterisation process relates to the object selected. Only the devices and
storage objects detected during the bus scan are displayed in the selection list. If only one
frequency inverter is connected and no storage address occupied, this parameter is not
displayed!
Value range: FI, S1 ... S5
Summary of Contents for SK 200E Series
Page 1: ...GB BU 0200 NORDAC SK 200E Frequency inverter manual Quick commissioning page 123...
Page 2: ...NORDAC SK 200E Manual 2 BU 0200 GB...
Page 138: ...NORDAC SK 200E Manual 138 Subject to technical alterations BU 0200 GB 5 4 6 Certificate...
Page 262: ...NORDAC SK 200E Manual 262 BU 0200 GB...
Page 263: ...10 Keyword index BU 0200 GB 263...
Page 264: ...NORDAC SK 200E Manual 264 BU 0200 GB Part No 607 2002 1310...
Page 265: ...The Nordac SK 200E is available to order from www inverterdrive com...