Table of possible error messages in the I/O extension module
Error number
Group
Details in
P170
Error
Text in the Parameter Box
Cause
Remedy
1000
EEPROM error
EMC interference on the SPI bus
Module faulty
E1000
1030
System bus, Bus Off
Check connections and cables
Ensure 24V power supply
Check Bus master.
2000 DIP
changed/fault
DIP switch configuration changed during operation
2001
DIP invalid config
uration
Illegal DIP switch setting
Check DIP switch setting. Note coding of analog inputs and
outputs!
E2000
2010 A
nalog
out
put
fault
Check switching of 10V reference voltage
Short circuit of analog output
Analog output overload (max. 10mA)
Calibration error (P152)
A range error has occurred during measurement
of the correction values
The measured values could not be saved in the
EEPROM