6 Parameterisation
BU 0200 GB
Subject to technical alterations
189
6.1.8
Information
(Frequency inverter)
Parameter
Setting value / Description / Note
Device
Supervisor
Parameter
set
P700
[-01]
...
[-03]
Actual operating status
Display of current messages for the actual operating status of the frequency inverter such as
errors, wanings or the cause of a switch-on block. For details of messages see Section 7
[-01] = Current fault,
shows the currently active (unacknowledged) error (Section 7.2.1)
[-02] = Actual warning,
shows any current warning message (Section 7.3)
[-03] = Reason FI blocked,
shows the reason for a currently active switch-on block
(Section 7.4)
0.0 ... 21.4
Note
SimpleBox:Only warning messages and errors
can be displayed with the Simplebox. Display of
the messages is encoded. The description of the codes (warning/error numbers) can be found
in the relevant table in Section 7.2.1, 7.3.
ParameterBox:
the ParameterBox displays the messages in plain text. The reason for any
switch-on block can also be displayed.
Bus:
The display of error messages at bus level is in decimal integer format. If the value is
divided by 10, the display corresponds to the description in Section 7.2.
Example: Display: 20
→
Error number: 2.0
P701
[-01]
...
[-05]
Last fault 1...5
0.0 ... 21.4
This parameter stores the last 5 faults. (Details Section 7)
With the SimpleBox, the corresponding memory location 1...5- (Array parameter) must be
selected and confirmed using the OK key to read the stored error code.
P702
[-01]
...
[-05]
Freq
uency
, last error 1...5
S
-400.0 ... 400.0 Hz
This parameter stores the output frequency that was being delivered at the time the fault
occurred. The values of the last 5 errors are stored.
With the SimpleBox, the corresponding memory location 1...5- (Array parameter) must be
selected and confirmed using the OK key to read the stored error code.
P703
[-01]
...
[-05]
Current, last error 1...5
S
0.0 ... 999.9 A
This parameter stores the output current that was being delivered at the time the fault occurred.
The values of the last 5 errors are stored.
With the SimpleBox, the corresponding memory location 1...5- (Array parameter) must be
selected and confirmed using the OK key to read the stored error code.
P704
[-01]
...
[-05]
Volt
age
, last error 1...5
S
0 ... 600 V AC
This parameter stores the output voltage that was being delivered at the time the fault occurred.
The values of the last 5 errors are stored.
With the SimpleBox, the corresponding memory location 1...5- (Array parameter) must be
selected and confirmed using the OK key to read the stored error code.
Summary of Contents for SK 200E Series
Page 1: ...GB BU 0200 NORDAC SK 200E Frequency inverter manual Quick commissioning page 123...
Page 2: ...NORDAC SK 200E Manual 2 BU 0200 GB...
Page 138: ...NORDAC SK 200E Manual 138 Subject to technical alterations BU 0200 GB 5 4 6 Certificate...
Page 262: ...NORDAC SK 200E Manual 262 BU 0200 GB...
Page 263: ...10 Keyword index BU 0200 GB 263...
Page 264: ...NORDAC SK 200E Manual 264 BU 0200 GB Part No 607 2002 1310...
Page 265: ...The Nordac SK 200E is available to order from www inverterdrive com...