GB
Value Function
Description
Signal
03
Phase seq. reversal
(Change rotation direction)
Causes the rotation field to change direction in combination with
Enable right or left.
High
04
1
Fixed frequency 1
The frequency from P465 [01] is added to the actual setpoint
value.
High
05
1
Fixed frequency 2
The frequency from P465 [02] is added to the actual setpoint
value.
High
06
1
Fixed frequency 3
The frequency from P465 [03] is added to the actual setpoint
value.
High
07
1
Fixed frequency 4
The frequency from P465 [04] is added to the actual setpoint
value.
High
If several fixed frequencies are actuated simultaneously, then they are added with the correct sign. In addition,
the analog setpoint (P400) and if required, the minimum frequency (P104) are added.
08
Param
eter
set switching 1
Selection of the active parameter set 1…4 (P100)
High
09
Maintain the freq
uency
During the acceleration or deceleration phase, a Low level will
cause the actual output frequency to be "held". A High level
allows the ramp to proceed.
Low
10
2
Voltage disable
The FI output voltage is switched off; the motor runs down freely.
Low
11
2
Quick stop
The FI reduces the frequency according to the programmed quick
stop time (P426).
Low
12
2
Fault acknowledgem
ent
Error acknowledgement with an external signal. If this function is
not programmed, a fault can also be acknowledged by a low
enable setting (P506).
0
Æ
1
Flank
13
2
PTC resistor input
Only with the use of a temperature monitor (bimetal switching
contact). Switch-off delay = 2sec, warning after 1 sec.
High
14
2
Remote control
With bus system control, low level switches the control to control
via control terminals.
High
15
Jog frequency
1
The fixed frequency value can be adjusted using the
HIGHER/LOWER and OK keys (P113), if control is via the
SimpleBox or ParameterBox.
High
16
Motor potentiometer
As in setting
09
, however, the frequency is not maintained below
the minimum frequency P104 and above the maximum frequency
P105.
Low
17
Para
meter
set switching 2
Selection of the active parameter set 1…4 (P100)
High
18
2
Watchdog
Input must see a high flank cyclically (P460), otherwise error
E012 will cause a shutdown. Function starts with the 1st High
flank.
0
Æ
1
Flank
19
... 20 reserved
21
...25 reserved for Posicon
26
Analog f
un
ct
ion
0-10V
Dig2+3
27
A
nalog
f
un
ct
ion
2-10V D
ig
2+3
28
A
nalog
f
un
ct
ion
5-10V D
ig
2+3
T
hese functio
n
s
can only
be
used for the d
igital i
nputs 2
(P420 [-02]) a
n
d
3 (P420 [-0
3
])
!
Via
DIN 2
and
DIN 3
impulses which are proportional to an analog
signal can be evaluated with this setting. The function of this
signal is determined in parameter P400 [-06] or [-07].
The conversion 0-10V to impulses can be carried out via the
Customer Unit SK CU/TU4-24V-... This module includes an
analog input and an impulse output (ADC).
In setting { 28 } a reversal of the direction of rotation takes place
with an analog value <5V.
An application example is described in Section 3.4.2.
Impulses
≈
1.6-
16kHz
30
Inhibit PID
Switching the PID controller / process controller function on and
off (High = ON)
High
... continued on the next page
Summary of Contents for SK 200E Series
Page 1: ...GB BU 0200 NORDAC SK 200E Frequency inverter manual Quick commissioning page 123...
Page 2: ...NORDAC SK 200E Manual 2 BU 0200 GB...
Page 138: ...NORDAC SK 200E Manual 138 Subject to technical alterations BU 0200 GB 5 4 6 Certificate...
Page 262: ...NORDAC SK 200E Manual 262 BU 0200 GB...
Page 263: ...10 Keyword index BU 0200 GB 263...
Page 264: ...NORDAC SK 200E Manual 264 BU 0200 GB Part No 607 2002 1310...
Page 265: ...The Nordac SK 200E is available to order from www inverterdrive com...