7 Status messages
BU 0200 GB
Subject to technical alterations
227
7.4 Table of possible reasons for the operating status "Switch-on block"
Group
Details in
P700 [-03]
Reason
Text in the Parameter Box
Cause
Remedy
0.1 Volt
age
blocked by IO
With the function "Block voltage" the parameterised input
(P420 / P480) is set to Low
Set input to "High"
Check signal cable (broken cable)
0.2
Quick stop by IO
With the function "Quick stop" the parameterised input
(P420 / P480) is set to Low
Set input to "High"
Check signal cable (broken cable)
0.3 Volt
age
blocked by bus
With bus operation (P509): Control word Bit 1 "Low"
0.4
Quick stop by bus
With bus operation (P509): Control word Bit 2 "Low"
I000
0.5
Enable at start
Enable signal (control word, Dig I/O or Bus I/O) was already
present during the initialisation phase (after mains "ON" or
control voltage "ON").
Only give enable signal after completion of initialisation (i.e.
when the FI is on standby)
Activation of "Automatic start" (P428)
I006
6.0 Charging
error
Charging relay not actuated, because
Mains / link voltage too low
Mains voltage failure
Evacuation run activated (Parameter (P420) / (P480))
I014
14.4 Abs
olute
encoder error
Absolute encoder not ready
Summary of Contents for SK 200E Series
Page 1: ...GB BU 0200 NORDAC SK 200E Frequency inverter manual Quick commissioning page 123...
Page 2: ...NORDAC SK 200E Manual 2 BU 0200 GB...
Page 138: ...NORDAC SK 200E Manual 138 Subject to technical alterations BU 0200 GB 5 4 6 Certificate...
Page 262: ...NORDAC SK 200E Manual 262 BU 0200 GB...
Page 263: ...10 Keyword index BU 0200 GB 263...
Page 264: ...NORDAC SK 200E Manual 264 BU 0200 GB Part No 607 2002 1310...
Page 265: ...The Nordac SK 200E is available to order from www inverterdrive com...