NORDAC SK 200E Manual
126
Subject to technical alterations BU
0200
GB
Details of DIP switches 5/4 and 3
Explanation: (values underlined in brackets) = (relevant parameter / source of function),
e.g.: Parameter (P420[01])
{curly
brackets}
=
{Function}
e.g.: {01} "Enable Right"
(See also Section 6:
→
Table behind parameter (P420), (P400) or (P434))
*
Default
setting
** only if available (Devices without function "Safe Stop")
Explanation: See table above
Note:
The functions of potentiometers P1 and P2 correspond to those of devices without an AS interface (see table above).
With DIP switches 5 and 4 in the OFF position (default setting), the digital inputs are also active. The functions then correspond to those of devices
without an AS interface (table above). In all other DIP switch combinations the functions of the digital inputs are deactivated.
ASi OUT1 and ASi OUT2 loop the signal level (High / Low) of digital inputs 1 and 2.
Applies to devices SK 205E, SK 215E (without AS interface on board)
DIP
Functions as per the list of digital functions (P420)
Functions as per the list of
analog functions (P400)
5 4 3
Dig 1
Dig 2
Dig 3
Dig 4**
Poti 1
Poti 2
off
off
off
(P420 [01])*
{01}
"Enable R"
(P420 [02])*
{02}
"Enable L"
(P420 [03])*
{04}
“Fixed freq. 1"
=5Hz (P465[01])
(P420 [05])*
{04}
“Fixed freq. 2"
=10Hz (P465[02])
(P400 [01])*
{01}
" F setpoint"
(P400 [02])*
{15}
"Ramp"
off on off
{01}
"Enable R"
{02}
"Enable L"
{26}
"F setpoint"
{12}
"Quit"
{05}
"F max"
{04}
"F min"
on
off
off
{45}
"3-on"
{49}
"3-off"
{47}
"Freq. +"
{48}
"Freq. -"
{05}
"F max"
{15}
"Ramp"
on on off
{50}
„F Arr Bit0
=5Hz (P465[01])
{51}
„F Arr Bit1“
=10Hz (P465[02])
{52}
„F Arr Bit2“
=20Hz (P465[03])
{53}
„F Arr Bit3“
=35Hz (P465[04])
{05}
"F max"
{15}
"Ramp"
The functions of the digital inputs are inactive (control via system bus), however, the
settings made in parameters (P420 [01 … 04]) result in the activation of the
correspondingly parameterised input, for the functions designated with ..² in the function
list (e.g.: {11}²= "Quick stop).
off
off on
(P420 [01])
no function
(P420 [02])
no function
(P420 [03])
{04} Fixed freq. 1"
=5Hz (P465[01])
(P420 [04])
{05} Fixed freq. 2"
=10Hz (P465[02])
(P400 [01])
{
01} " F setpoint"
(P400 [02])
{15}
"Ramp"
off on on
{14}
"Remote
control"
"Encoder track
A"
"Encoder track
B"
{01}
"Enable R"
{01}
"F
setpoint"
{05}
"F max"
on
off on
{14}
"Remote
control"
{01}
"Enable R"
{10}
"Block"
{66}
"Release
brake"
{01}
"F
setpoint"
{05}
"F max"
on on on
{14}
"Remote
control"
{51}
„F Arr Bit1“
=10Hz (P465[02])
{52}
„F Arr Bit2“
=20Hz (P465[03])
{53}
„F Arr Bit3“
=35Hz (P465[04])
{05}
"F max"
{15}
"Ramp"
Applies to devices SK 225E, SK 235E (with AS interface on board)
DIP
Functions as per the list of digital functions (P420)
Functions as per the list of digital outputs (P434)
5 4 3
ASi
In1
ASi
In2
ASi
In3
ASi
In4
ASi
Out1
ASi
Out2
ASi
Out3
ASi
Out4
off off off
(P480 [01])*
{01}
"Enable
R"
(P480 [02])*
{02}
"Enable
L"
(P480 [03])
{04}
Fixed
freq. 1"
=5Hz (P465[01])
(P480 [04])*
{12}
"Quit"
(P481 [01])*
{07}
"Error"
(P481 [02])*
{18}
"Standby"
"DigIn1" "DigIn2"
off on off
{04}
"Fixed
freq. 1"
=5Hz (P465[01])
{05}
"Fixed
freq. 2"
=10Hz (P465[02])
{06}
"Fixed
freq. 3"
=20Hz (P465[03])
{07}
"Fixed
freq. 4"
=35Hz (P465[04])
{07}
"Error"
{18}
"Standby"
"DigIn1" "DigIn2"
on off off
{01}
"Enable R"
{02}
"Enable L"
{47}
"Freq. +"
{48}
"Freq. -"
{07}
"Error"
{18}
"Standby"
"DigIn1" "DigIn2"
on on off
{51}
"F Arr B1"
=10Hz (P465[02])
{52}
"F Arr B2"
=20Hz (P465[03])
{53}
"F Arr B3"
=35Hz (P465[04])
{14}
"Remote
control"
{07}
"Error"
{18}
"Standby"
"DigIn1" "DigIn2"
The functions of the digital inputs are inactive (control via system bus),
however, the settings made in parameters (P480 [01 … 04]) result in the
activation of the correspondingly parameterised bits, for the functions
designated with ..² in the function list (e.g.: {11}²= "Quick stop).
off off on
(P480 [01])no
function
(P480 [02])
no function
(P480 [03])
{04}
Fixed
freq. 1"
=5Hz (P465[01])
(P480 [04])
{12}
"Quit"
(P481 [01])
{07}
"Error"
(P481 [02])
{18}
"Standby"
"DigIn1" "DigIn2"
off on on
{14}
"Remote
control"
{04}
"Fixed
freq. 1"
=5Hz (P465[01])
{05}
"Fixed
freq. 2"
=10Hz (P465[02])
{06}
"Fixed
freq. 3"
=20Hz (P465[03])
{07}
"Error"
{18}
"Standby"
"DigIn1" "DigIn2"
on off on
{14}
"Remote
control"
{01}
"Enable R"
{47}
"Freq. +"
{48}
"Freq. -"
{07}
"Error"
{18}
"Standby"
"DigIn1" "DigIn2"
on on on
{14}
"Remote
control"
{50}
"F Arr B0"
=5Hz (P465[01])
{51}
"F Arr B1"
=10Hz (P465[02])
{52}
"F Arr B2"
=20Hz (P465[03])
{07}
"Error"
{18}
"Standby"
"DigIn1" "DigIn2"
Summary of Contents for SK 200E Series
Page 1: ...GB BU 0200 NORDAC SK 200E Frequency inverter manual Quick commissioning page 123...
Page 2: ...NORDAC SK 200E Manual 2 BU 0200 GB...
Page 138: ...NORDAC SK 200E Manual 138 Subject to technical alterations BU 0200 GB 5 4 6 Certificate...
Page 262: ...NORDAC SK 200E Manual 262 BU 0200 GB...
Page 263: ...10 Keyword index BU 0200 GB 263...
Page 264: ...NORDAC SK 200E Manual 264 BU 0200 GB Part No 607 2002 1310...
Page 265: ...The Nordac SK 200E is available to order from www inverterdrive com...