background image

   1

This guide is applicable to the global IEC and NEC North American installations

.

Safety instructions

WARNING!

 Obey these instructions. If you ignore them, injury or death, or damage to the equipment can occur. If 

you are not a qualified electrical professional, do not do electrical installation or maintenance work.

WARNING!

 If you activate the automatic fault reset or automatic restart functions of the drive control program, 

make sure that no dangerous situations can occur. These functions reset the drive automatically and continue 

operation after a fault or supply break. If these functions are activated, the installation must be clearly marked as 

defined in IEC/EN 61800-5-1, subclause 6.5.3, for example, “THIS MACHINE STARTS AUTOMATICALLY”.

• 

Do not do work on the drive, motor cable, motor, or control cables when the drive is connected to the input power. 

Before you start the work, isolate the drive from all dangerous voltage sources and measure that there are no 

dangerous voltages. Always wait for 5 minutes after disconnecting the input power to let the intermediate circuit 

capacitors discharge.

• 

Do not do work on the drive when a rotating permanent 

magnet motor is connected to it. A rotating permanent 

magnet motor energizes the drive, including its input and 

output terminals.

• 

Make sure that debris from drilling, cutting and grinding. 

does not enter the drive.

• 

Frames R4…R9: Use the lifting eyes of the drive when you 

lift the drive. Do not tilt the drive. The drive is heavy and 

its center of gravity is high. An overturning drive can 

cause physical injury.

1. Unpack the drive

Keep the drive in its package until you are ready to install it. After unpacking, protect the drive from dust, debris and 

moisture. Make sure that these items are included: cable/conduit box (frames R5…R9 of IP21 [UL Type 1]), drive, mounting 

template, control panel, quick installation and start-up guide, multilingual residual voltage warning stickers, hardware and 

firmware manuals (if ordered), options in separate packages (if ordered). Make sure that there are no signs of damage to 

the items.

2.  Reform the capacitors

If the drive has not been powered up for a year or more, you must reform the DC link capacitors. See 

Related documents

 or 

contact ABB technical support.

3.  Select the cables and fuses

• 

Select the power cables. Obey the local regulations.

Input power cable:

 Use symmetrical shielded cable (VFD cable) for the best EMC performance. NEC installations: 

Conduit with continuous conductivity is also allowed and must be grounded on both ends.

Motor cable:

 

ABB recommends symmetrically shielded VFD motor cable to reduce bearing current and wear and 

stress on motor insulation and to provide the best EMC performance. Although not recommended, conductors 

inside continuously conductive conduit is allowed in NEC installations. Ground conduit on both ends.

Power cable types:

 IEC installations: Use copper cables. Aluminum cables can only be used with frame sizes R5…R9. 

NEC installations: Only copper conductors are allowed.

Current rating:

 max. load current.

Voltage rating (minimum):

 IEC installations: 600 V AC cable is accepted for up to 500 V AC, 750 VAC cable is 

accepted for up to 600 V AC, 1000 V AC cable is accepted for up to 690 V AC. NEC installations: 600 V AC for 230 V AC 

Documentation in other languages

Ecodesign information (EU 2019/

1781)

About this document

3AXD50000754618 Rev A EN 

2021-06-30

© 2021 ABB. All rights reserved. 

Original instructions.

ABB INDUSTRIAL DRIVES

ACS880-01

Quick installation and start-up guide 

Summary of Contents for ACS880-01 Series

Page 1: ...After unpacking protect the drive from dust debris and moisture Make sure that these items are included cable conduit box frames R5 R9 of IP21 UL Type 1 drive mounting template control panel quick ins...

Page 2: ...erial The installation surface is as close to vertical as possible and strong enough to support the drive There is sufficient free space around the drive for cooling maintenance and operation For the...

Page 3: ...the measurement again Frame Symmetrically grounded TN S systems center grounded wye Corner grounded delta and midpoint grounded delta systems IT systems ungrounded or high resistance grounded TT syste...

Page 4: ...e c Shield of a VFD shielded cable Ground the shield 360 under drive s grounding clamp then twist with the ground conductors and connect under the drive s ground terminal Ground the shield also 360 a...

Page 5: ...to Terminal data For frames R1 R3 Ground the cable shields 360 degrees in the Romex clamp IP21 Type 1 units For IP55 Type 12 ground the cable shield 360 degrees on grounding shelf as shown in R4 R5 a...

Page 6: ...als as possible to prevent inductive coupling 1 Cut a hole into the rubber grommet and slide the grommet onto the cable 2 Ground the outer shield of the cable 360 degrees under the grounding clamp Kee...

Page 7: ...22 COM 23 NO 31 NC Faulted 1 250 V AC 30 V DC 2 A 32 COM 33 NO XD24 Digital interlock 1 DIIL Run enable 2 24VD 24 V DC 200 mA 1 3 DICOM Digital input ground 4 24VD 24 V DC 200 mA 1 5 DIOGND Digital in...

Page 8: ...1 5 N m 1 5 N m R1 R3 R4 R9 Note Use an un used ground clamp screw If none available ground as shown 1 2 3 2 2 Note The illustration shows frame R2 All frame sizes are similar M4 8 Torx T20 2 N m 17 l...

Page 9: ...torques refer to Terminal data Frames R4 R5 Install the EMC shroud separating the input and output cabling if not installed yet If brake chopper is in use Connect the brake resistor conductors to the...

Page 10: ...xt Use the arrow keys and to move the cursor or change values depending on the active view Key shows a context sensitive help page 1 Power up the drive Make sure that you have the motor name plate dat...

Page 11: ...in the master station 58 05 Parity 8 EVEN 1 default Selects the parity and stop bit setting Use the same setting as in the master station 58 06 Communication control Refresh settings Validates any ch...

Page 12: ...880 01 Frame size Nominal ratings Fuses3 Typical power cable Typical power loss 8 Input current Output current Motor power1 gG fuse4 DIN 43620 aR fuse2 4 DIN 43620 ULclass T5 6 7 Copper I1 I2 Pn ABB t...

Page 13: ...0 170M6814D JJS 500 2 3 120 2 4 0 4800 414A 5 R9 414 414 250 350 OFAF3H630 170M8554D JJS 600 2 3 150 2 300 MCM 5662 Un 3 phase 575 V 07A4 7 R3 7 0 7 0 5 0 JJS 15 14 106 09A9 7 R3 9 4 9 4 7 5 JJS 20 14...

Page 14: ...M 30 22 1 185 350 MCM 9 8 7 2 R7 1 54 2 13 95 240 25 150 3 0 400 MCM 4 300 MCM 40 30 29 5 22 1 185 350 MCM 9 8 7 2 R8 2 45 1 77 2 50 150 2 1 0 300 MCM 40 29 5 2 185 2 350 MCM 9 8 7 2 R9 2 54 2 13 2 95...

Page 15: ...ledge of the safety function The test procedures and report must be documented and signed by this person Validation instructions of the STO function can be found in the drive hardware manual Technical...

Page 16: ...ucts ACS880 01 11 31 ACS880 04 04F M04 14 34 Safe Torque Off Safe stop 1 Safe stop emergency Safely limited speed Safe maximum speed Safe brake control Prevention of unexpected start up with FSO 12 op...

Reviews: