Chapter 2
Analog Input Timing/Control
DAQ-STC Technical Reference Manual
2-72
©
National Instruments Corporation
AI_SI2_Load_B
bits: <0..15>
type: Write
in: AI_SI2_Load_B_Register
address: 25
This bitfield is load register B for the SI2 counter. If load register B is the selected SI2 load
register, the SI2 counter loads the value contained in this bitfield on AI_SI2_Load and on
SI2_TC. Related Bitfields: AI_SI2_Next_Load_Source_St, AI_SI2_Load.
AI_SI2_Next_Load_Source_St
bit: 12
type: Read
in: AI_Status_2_Register
address: 5
This bit indicates the next load source of the SI2 counter:
0: Load register A.
1: Load register B.
AI_SI2_Q_St
bits: <8..9>
type: Read
in: Joint_Status_1_Register
address: 27
This bitfield reflects the state of the SI2 control circuit:
0: WAIT 1.
1: CNT.
2: WAIT 2.
, for more information on the SI2 control circuit.
AI_SI2_Reload_Mode
bit: 8
type: Write
in: AI_Mode_2_Register
address: 13
This bit selects the reload mode for the SI2 counter:
0: No automatic change of the SI2 load register.
1: Alternate first period on every STOP.
Set this bit to 1 in the internal CONVERT mode to make the time interval between the
START trigger and the first CONVERT different from the time interval between
CONVERTs.
AI_SI2_Save_Value
bits: <0..15>
type: Read
in: AI_SI2_Save_Register
address: 25
This bitfield reflects the contents of the SI2 counter. Reading from this bitfield while the SI2
counter is counting may result in an erroneous value.