Parameters
(N) Operation via communication and its settings
FR-F800
5 - 483
Preset Single Register (writing of data to holding registers) (H06 or 06)
●
The content of the "system environmental variables" and "inverter parameters" assigned to the
holding register area (refer to the register list (page 5-488)) can be written.
●
Query message
●
Normal response (Response message)
●
Query message setting
●
Content of normal response
With a normal response, the content is the same as
to
(including the CRC check) query
messages.
In the case of broadcast communication, no response is returned.
Slave Address
Function
Register Address
Preset Data
CRC Check
(8 bits)
H06
(8 bits)
H
(8 bits)
L
(8 bits)
H
(8 bits)
L
(8 bits)
L
(8 bits)
H
(8 bits)
Slave Address
Function
Register Address
Preset Data
CRC Check
(8 bits)
H06
(8 bits)
H
(8 bits)
L
(8 bits)
H
(8 bits)
L
(8 bits)
L
(8 bits)
H
(8 bits)
Message
Description
Slave Address
Set the address to send messages to. Setting "0" enables broadcast communication.
Function Set
H06.
Register Address
Set the address from data is written to the holding register.
Register address = holding register address (decimal) - 40001
For example, when register address 0001 is set, data is written to holding register
address 40002.
Preset Data
Set the data to write to the holding register. Write data is fixed at 2 bytes.
Tab. 5-245:
Description of the query message
Example
쑴
Write 60 Hz (H1770) to 40014 (running frequency) of slave address 5 (H05).
Query message
Normal response (Response message)
Same data as query message.
쑶
NOTE
With broadcast communication, no response is generated even if a query is executed, so when the
next query is made, it must be made after waiting for the inverter data processing time after the
previous query is executed.
Slave Address
Function
Register Address
Preset Data
CRC Check
H05
(8 bits)
H06
(8 bits)
H00
(8 bits)
H0D
(8 bits)
H17
(8 bits)
H70
(8 bits)
H17
(8 bits)
H99
(8 bits)
Summary of Contents for FR-F800
Page 2: ......
Page 4: ......
Page 28: ...Related manuals Introduction 1 8 ...
Page 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Page 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 806: ...Outline dimension drawings Specifications 8 26 ...
Page 833: ......