(M) Monitor display and monitor output signal
Parameters
5 - 228
41
141
FB
Speed detection
Output when the actual motor rotations
per minute (estimated rotations per
minute) reaches Pr. 42 (Pr. 50.
Pr. 42, Pr. 50
42
142
FB2
Second speed detection
45
145
RUN3
Inverter running and start
command is ON
Output while the inverter is running and
the start command is ON.
⎯
46
146
Y46
During deceleration at
occurrence of power
failure (retained until
release)
Output after the power-failure
deceleration function operates.
(Retained until cancelled.)
Pr. 261 to
Pr. 266
47
147
PID
During PID control
activated
Output during PID control.
Pr. 127 to
Pr. 134, Pr. 575
to Pr. 577
48
148
Y48
PID deviation limit
Output when the absolute deviation
value exceeds the limit value.
Pr. 127 to
Pr. 134, Pr. 553,
Pr. 554
49
149
Y49
During pre-charge
operation
Output during pre-charge operation.
Pr. 127 to
Pr. 134, Pr. 241,
Pr. 553, Pr. 554,
Pr. 575 to
Pr. 577, Pr. 753
to Pr. 769, C42
to C45
50
150
Y50
During second pre-
charge operation
51
151
Y51
Pre-charge time over
Output when the pre-charge operation
reaches the time limit set in Pr. 764 or Pr.
769.
52
152
Y52
Second pre-charge time
over
53
153
Y53
Pre-charge level over
Output when the measured value before
reaching the ending time during pre-
charge operation is higher than the
detection level set in Pr. 763 or Pr. 768.
54
154
Y54
Second pre-charge level
over
57
157
IPM
During PM motor control
Output while the control method is PM
motor control.
Pr. 71, Pr. 80,
Pr. 998
64
164
Y64
During retry
Output during retry processing.
Pr. 65 to Pr. 69
65
165
Y65
Emergency drive in
operation
Output during emergency drive
operation
Pr. 514, Pr. 515,
Pr. 523, Pr. 524,
Pr. 1013
66
166
ALM3
Fault output during
emergency drive
Output when a fault occurs during
emergency drive operation.
67
167
Y67
Output when the power failure time
deceleration-to-stop function is activated
during output shutoff due to power
failure or undervoltage.
Pr. 261 to
Pr. 266
68
168
EV
24 V external power
supply operation
Output while operating with a 24 V
power supply input from an external
source.
⎯
70
170
SLEEP
PID output interruption
Output during PID output suspension
function operation.
Pr. 127 to
Pr. 134, Pr. 575
to Pr. 577
71
171
RO1
Commercial power
supply side motor 1
connection
Output depending on the motor drive
conditions when the multi-pump
function is used.
Pr. 575 to
Pr. 591
72
172
RO2
Commercial power
supply side motor 2
connection RO2
73
173
RO3
Commercial power
supply side motor 3
connection RO3
74
174
RO4
Commercial power
supply side motor 4
connection
75
175
RIO1
Inverter side motor 1
connection RIO1
76
176
RIO2
Inverter side motor 2
connection RIO2
77
177
RIO3
Inverter side motor 3
connection RIO3
78
178
RIO4
Inverter side motor 4
connection RIO4
Setting
Signal
name
Function
Operation
Related
parameter
Refer to
page
Positive
logic
Negative
logic
Tab. 5-101:
Output terminal function assignment (2)
Summary of Contents for FR-F800
Page 2: ......
Page 4: ......
Page 28: ...Related manuals Introduction 1 8 ...
Page 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Page 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 806: ...Outline dimension drawings Specifications 8 26 ...
Page 833: ......