(M) Monitor display and monitor output signal
Parameters
5 - 244
●
When Pr. 54 "FM/CA terminal function selection" = "87, 88, 89, or 90" (remote output), the CA type
inverter can output any analog current from the terminal CA.
●
Terminal CA output [mA] = 20 [mA] × (analog remote output value – 1000)/100
Where the output range is 0 to 20 mA.
●
When Pr. 158 "AM terminal function selection" = "87, 88, 89, or 90", an analog voltage can be output
from the terminal AM.
●
Terminal AM output [V] = 10 [V] × (analog remote output value – 1000)/100
The output range is –10 V to +10 V regardless of the Pr. 290 "Monitor negative output selection"
setting.
I002634E
Fig. 5-107:
Terminal CA output
I002635E
Fig. 5-108:
Terminal AM output
20
1100
1200
800
1000
0
Output current [mA]
Analog remote output value [%]
Terminal CA
10
1100
1200
-10
900
800
1000
0
Terminal AM
Analog remote output value [%]
Output voltage [V]