Peripheral devices
Installation and wiring
2 - 10
●
400 V class
Assumes the use of an IPM motor MM-EFS/MM-THE4 or a Mitsubishi 4-pole standard motor with
the power supply voltage of 400 V AC 50 Hz.
Select an MCCB according to the power supply capacity.
Install one MCCB per inverter.
For the use in the United States or Canada, provide the appropriate UL and cUL listed fuse or UL489
molded case circuit breaker (MCCB) that is suitable for branch circuit protection. (Refer to the
Installation Guideline.)
Motor
output
[kW]
Applicable inverter
model
Molded case circuit breaker (MCCB)
or
earth leakage circuit breaker (ELB)
(NF, NV type)
Input-side magnetic contactor
Power factor improving (AC or DC)
reactor
Power factor improving (AC or DC)
reactor
Without
With
Without
With
0.75
FR-F840-00023(0.75K)
5A
5A
S-T10
S-T10
1.5
FR-F840-00038(1.5K)
10A
10A
S-T10
S-T10
2.2
FR-F840-00052(2.2K)
10A
10A
S-T10
S-T10
3.7
FR-F840-00083(3.7K)
20A
15A
S-T10
S-T10
5.5
FR-F840-00126(5.5K)
30A
20A
S-T21
S-T12
7.5
FR-F840-00170(7.5K)
30A
30A
S-T21
S-T21
11
FR-F840-00250(11K)
50A
40A
S-T21
S-T21
15
FR-F840-00310(15K)
60A
50A
S-N35
S-T21
18.5
FR-F840-00380(18.5K)
75A
60A
S-N35
S-N35
22
FR-F840-00470(22K)
100A
75A
S-N35
S-N35
30
FR-F840-00620(30K)
125A
100A
S-N50
S-N50
37
FR-F840-00770(37K)
150A
125A
S-N65
S-N50
45
FR-F840-00930(45K)
175A
150A
S-N80
S-N65
55
FR-F840-01160(55K)
200A
175A
S-N150
S-N80
75
FR-F840-01800(75K)
—
225A
—
S-N150
90
FR-F840-01800(75K)
—
225A
—
S-N150
110
FR-F840-02160(90K)
—
225A
—
S-N180
132
FR-F840-02600(110K)
—
350A
—
S-N220
150
FR-F840-03250(132K)
—
400A
—
S-N300
160
FR-F840-03250(132K)
—
400A
—
S-N300
185
FR-F840-03610(160K)
—
400A
—
S-N300
220
FR-F840-04320(185K)
—
500A
—
S-N400
250
FR-F840-04810(220K)
—
600A
—
S-N600
280
FR-F840-05470(250K)
—
600A
—
S-N600
315
FR-F840-06100(280K)
—
700A
—
S-N600
355
FR-F840-06830(315K)
—
800A
—
S-N800
Tab. 2-5:
Breakers and contactors (SLD rating, 400 V class)
Fig. 2-5:
Installation of the breakers
I002770E
INV
MCCB
INV
MCCB
M
M
Summary of Contents for FR-F800
Page 2: ......
Page 4: ......
Page 28: ...Related manuals Introduction 1 8 ...
Page 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Page 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 806: ...Outline dimension drawings Specifications 8 26 ...
Page 833: ......