(H) Protective function parameter
Parameters
5 - 170
Emergency drive status monitor
●
Set "68" in Pr. 52, Pr. 774 to Pr. 776, Pr. 992 to monitor the status of the emergency drive on the
operation panel.
●
Description of the status monitor
The first digit remains the same as the previous numerical value (fault condition).
Operation
panel
indication
Description
Emergency drive setting
Emergency drive operating status
0
Emergency drive function
setting is not available.
—
1
Electronic bypass during
emergency drive operation
is disabled.
During normal operation
2
During emergency
drive operation
Operating properly
3
A certain alarm is occurring.
4
A critical fault is occurring. The operation is being
continued by the retry.
5
A critical fault is occurring. The continuous operation
is not allowed due to output shutoff.
11
Electronic bypass during
emergency drive operation
is enabled.
During normal operation
12
During emergency
drive operation
Operating properly
13
A certain alarm is occurring.
14
A critical fault is occurring. The operation is being
continued by the retry.
15
A critical fault is occurring. The continuous operation
is not allowed due to output shutoff.
2
Electronic bypass is started during emergency drive (during acceleration/
deceleration to the switchover frequency).
3
During electronic bypass during emergency drive (waiting during the
interlock time).
4
During commercial power supply operation during emergency drive
Tab. 5-78:
Emergency drive status monitor description
NOTES
When the "retry" (Pr. 523 = "2
, 3
") is selected, it is recommended to use the automatic
restart after instantaneous power failure function at the same time.
Parameter setting is not available during emergency drive operation.
To return to the normal operation during emergency drive operation, do the following:
(The operation will not be returned to normal only by turning OFF the X84 signal.)
●
Reset the inverter, or turn the power supply OFF.
●
Clear a fault by turning ON the X51 signal while the sequence function is enabled (when the
protective function is activated).
The operation is switched over to the commercial power supply operation in case of the following
during emergency drive operation:
●
24 V external power supply operation
●
Power failure status or operation with the power supplied through R1/S1
●
Undervoltage
While the electronic bypass sequence is set or when the operation is performed with the power
supplied through R1/S1, when Pr. 30 = "2", the emergency drive function is disabled.
Summary of Contents for FR-F800
Page 2: ......
Page 4: ......
Page 28: ...Related manuals Introduction 1 8 ...
Page 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Page 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 806: ...Outline dimension drawings Specifications 8 26 ...
Page 833: ......