Parameters
(M) Monitor display and monitor output signal
FR-F800
5 - 207
Monitor description list (Pr. 54, Pr. 158)
●
Set Pr. 54 "FM/CA terminal function selection" for the monitor to be output to the terminal FM
(pulse train output) and terminal CA (analog current output).
●
Set Pr. 158 "AM terminal function selection" for the monitor to be output to the terminal AM
(analog voltage output). Output with a negative sign can be made (-10 V DC to +10 V DC) from
the terminal AM. "
" in the [Negative (-) output] indicates the output value is negative at the
terminal AM. (For setting of the output with/without minus sign, refer to page 5-206.)
●
Refer to the following table and set the monitor to be displayed. (Refer to page 5-194 for the
monitor description.)
Types of monitor
Unit
Pr. 54
(FM/CA)
Pr. 158 (AM)
setting
Terminal
FM, CA, AM
Full-scale value
Negative
(-) output
Remarks
Output frequency
0.01 Hz
1
Pr. 55
Output current
0.01 A/0.1 A
2
Pr. 56
Output voltage
0.1 V
3
200 V class: 400 V
400 V class: 800 V
Frequency setting value
0.01 Hz
5
Pr. 55
Running speed
1 (r/min)
6
Value is Pr. 55
converted by Pr. 37,
Pr. 144.
(Refer to page 5-191.)
Refer to page 5-191 for the
running speed monitor.
Motor torque
0.1%
7
Pr. 866
Converter output
voltage
0.1 V
8
200 V class: 400 V
400 V class: 800 V
⎯
⎯
9
⎯
For manufacturer setting.
Do not set.
Electronic thermal O/L
relay load factor
0.1%
10
Electronic thermal
O/L relay operation
level (100%)
Output current peak
value
0.01 A/0.1 A
11
Pr. 56
Converter output
voltage peak value
0.1 V
12
200 V class: 400 V
400 V class: 800 V
Input power
13
Rated inverter power
× 2
Output power
14
Rated inverter power
× 2
Load meter
0.1%
17
Pr. 866
Motor excitation current
0.0 1 A/
0.1 A
18
Pr. 56
Reference voltage
output
⎯
21
⎯
Terminal FM:
1440 pulses/s is output
when Pr. 291 = 0,1.
50 k pulses/s is output when
Pr. 291 ≠ 0,1.
Terminal CA:
output is 20 mA
Terminal AM:
output is 10 V.
Motor load factor
0.1%
24
200%
Motor output
34
Rated motor capacity
Energy saving effect
Changeable
by parameter
setting
50
Inverter capacity
Regarding the energy
saving monitor, refer to
page 5-57
Tab. 5-96:
Monitor description list (1)
Summary of Contents for FR-F800
Page 2: ......
Page 4: ......
Page 28: ...Related manuals Introduction 1 8 ...
Page 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Page 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 806: ...Outline dimension drawings Specifications 8 26 ...
Page 833: ......