Parameters
(A) Application parameters
FR-F800
5 - 415
Adjustment of restart coasting time (Pr. 57)
●
Coasting time is the time from the motor speed detection to the restart operation start.
●
To enable restart operation, set "0" to Pr. 57 "Restart coasting time". If "0" is set to Pr. 57, the coasting
time is automatically set to the following value. Generally, this setting does not interfere with
inverter operation.
●
Inverter operation is sometimes hindered by the size of the moment of inertia (J) of the load or
running frequency. Adjust this coasting time within the range 0.1 s to 30 s to match the load
specification.
●
Set the waiting time when the sine wave filter is used (Pr. 72 "PWM frequency selection" = "25")
to 3 s or more.
Restart cushion time (Pr. 58)
●
The cushion time is the time takes to raise the voltage to the level required for the specified speed
after the motor speed detection (output frequency before instantaneous power failure when
Pr. 162 = "1 or 11").
●
Normally, the motor runs at the initial value as it is. However, adjust to suit the moment of inertia
(J) of the load or the size of the torque.
Pr. 162
setting
200 V class FR-F820-
00046
00077
00105
00167
00250
00340
00490
00630
00770
00930
01250
01540
01870
02330
03160
(0.75K) (1.5K)
(2.2K)
(3.7K)
(5.5K)
(7.5K)
(11K)
(15K)
(18.5K)
(22K)
(30K)
(37K)
(45K)
(55K) (75K) or
higher
400 V class FR-F840-
00023
00038
00052
00083
00126
00170
00250
00310
00380
00470
00620
00770
00930
01160
01800
(0.75K) (1.5K)
(2.2K)
(3.7K)
(5.5K)
(7.5K)
(11K)
(15K)
(18.5K)
(22K)
(30K)
(37K)
(45K)
(55K) (75K) or
higher
Other than
3, 13
0.5
1
3
5
3, 13
1
2
3
5
Tab. 5-204:
Restart waiting time
Summary of Contents for FR-F800
Page 2: ......
Page 4: ......
Page 28: ...Related manuals Introduction 1 8 ...
Page 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Page 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 806: ...Outline dimension drawings Specifications 8 26 ...
Page 833: ......