Protective functions
Check first when you have a trouble
FR-F800
6 - 37
6.6.8
Speed varies during operation
Under Advanced magnetic flux vector control the output frequency varies between 0 and 2 Hz as the
load fluctuates. This is a normal operation and not a fault.
Check
points
Possible cause
Countermeasure
Refer to
page
Load
Load varies during an operation.
Select Advanced magnetic flux vector control.
Input
signal
Frequency setting signal is varying.
Check the frequency setting signal.
⎯
The frequency setting signal is affected by
EMI.
Set filter to the analog input terminal using
Pr. 74 "Input filter time constant", Pr. 822 "Speed
setting filter 1".
Take countermeasures against EMI, such as
using shielded wires for input signal lines.
Malfunction is occurring due to the
undesirable current generated when the
transistor output unit is connected.
Use terminal PC (terminal SD when source
logic) as a common terminal to prevent a
malfunction caused by undesirable current.
Multi-speed command signal is chattering.
Take countermeasures to suppress chattering.
⎯
Parameter
setting
Fluctuation of power supply voltage is too
large.
Under V/F control, change the Pr. 19 "Base
frequency voltage" setting (approximately by
3%).
Pr. 80 "Motor capacity" and Pr. 81 "Number
of motor poles" are not appropriate for the
motor capacity under Advanced magnetic
flux vector control, or PM motor control.
Check the settings of Pr. 80 and Pr. 81.
Wiring length exceeds 30 m when
Advanced magnetic flux vector control, or
PM motor control is selected.
Perform offline auto tuning.
Under V/F control, wiring is too long and a
voltage drop occurs.
In the low-speed range, set 0.5% in Pr. 0 "Torque
boost".
Change the control method to Advanced
magnetic flux vector control.
Hunting occurs by the generated vibration,
for example, when structural rigidity at load
side is insufficient.
Disable automatic control functions, such as the
energy saving operation, fast-response current
limit operation regeneration avoidance
function, Advanced magnetic flux vector
control stall prevention, and online auto tuning.
Under PID control, set smaller values to Pr. 129
"PID proportional band" and Pr. 130 "PID
integral time".
Adjust so that the control gain decreases and
the level of safety increases.
⎯
Change Pr. 72 "PWM frequency selection"
setting.
Summary of Contents for FR-F800
Page 2: ......
Page 4: ......
Page 28: ...Related manuals Introduction 1 8 ...
Page 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Page 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 806: ...Outline dimension drawings Specifications 8 26 ...
Page 833: ......