(E) Environment setting parameters
Parameters
5 - 94
5.4.20
Current average value monitor signal
The output current average value during constant-speed operation and the maintenance timer value
are output to the current average value monitor signal (Y93) as a pulse. The output pulse width can be
used in a device such as the I/O unit of a programmable controller as a guideline for the maintenance
time for mechanical wear, belt stretching, or deterioration of devices with age.
The pulse is repeatedly output during constant-speed operation in cycles of 20 s to the Current av-
erage monitor signal (Y93).
Initial value for the FR-F820-02330(55K) or lower and FR-F840-01160(55K) or lower.
Initial value for the FR-F820-03160(75K) or higher and FR-F840-01800(75K)) and higher.
I002551E
Fig. 5-12:
Monitoring the maintenance timer and current average value
Pr.
Name
Initial
value
Setting range
Description
555
E720
Current average time
1 s
0.1 to 1 s
Set the time for calculating the
average current during start pulse
output (1 s).
556
E721
Data output mask time
0 s
0 to 20 s
Set the time for not obtaining
(masking) transitional state data.
557
E722
Current average value
monitor signal output
reference current
Rated
inverter
current
0 to 500 A
Set the reference (100%) for
outputting the output current
average value signal.
0 to 3600 A
Maintenance
time
Parts have
reached their life
Input unit
Output unit
Inverter
Programmable controller
Summary of Contents for FR-F800
Page 2: ......
Page 4: ......
Page 28: ...Related manuals Introduction 1 8 ...
Page 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Page 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 806: ...Outline dimension drawings Specifications 8 26 ...
Page 833: ......