(C) Motor constant parameters
Parameters
5 - 318
Parameters in which tuning results are set after tuning
Tuning adjustment (Pr. 1002)
The overcurrent protective function may be activated during Lq tuning for an easily magnetically sat-
urated motor (motor with a large Lq decay ratio). In such case, adjust the target flowing current used
for tuning with Pr. 1002 "Lq tuning target current adjustment coefficient".
Changing the motor constants
●
If the motor constant is known, the motor constant can be set directly or set using data measured
through offline auto tuning.
●
According to the Pr. 71 (Pr. 450) setting, the range of the motor constant parameter setting values
and units can be changed. The setting values are stored in the EEPROM as motor constant
parameters, and two types of motor constants can be stored.
First
motor
Pr.
Second
motor
Pr.
Name
Other than
MM-EFS/MM-THE4
Pr. 96 (Pr.4 63) = 1
V/F control or
MM-EFS/MM-THE4
Pr. 96 (Pr. 463) = 11
Description
90
458
Motor constant (R1)
Resistance per phase
92
460
Motor constant (L1)/
d-axis inductance (Ld)
⎯
d-axis inductance
93
461
Motor constant (L2)/
q-axis inductance (Lq)
⎯
q-axis inductance
711
739
Motor Ld decay ratio
⎯
d-axis inductance
decay ratio
712
740
Motor Lq decay ratio
⎯
q-axis inductance
decay ratio
717
741
Starting resistance tuning
compensation
721
742
Starting magnetic pole
position detection pulse
width
⎯
When the setting
value is 10000 or
more: With polarity
inversion for
compensation,
voltage pulse
(Pr. setting minus
10000)
μ
s
859
860
Torque current/
Rated PM motor current
⎯
96
463
Auto tuning setting/status
Tab. 5-150:
Setting of motor constants after tuning
Summary of Contents for FR-F800
Page 2: ......
Page 4: ......
Page 28: ...Related manuals Introduction 1 8 ...
Page 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Page 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 806: ...Outline dimension drawings Specifications 8 26 ...
Page 833: ......