(A) Application parameters
Parameters
5 - 390
●
Alternative system (Pr. 579 = "1"), direct system (Pr. 579 = "2"),
alternative direct system (Pr. 579 = "3")
When driving three or more motors, use the plug-in option (FR-A8AR).
Always provide mechanical interlocks for the MC.
The applied output signal terminals differ by the settings of Pr. 190 to Pr. 196 (output terminal
function selection).
The applied input signal terminals differ by the settings of Pr. 178 to Pr. 189 (input terminal function
selection).
"
The applied output signal terminals differ by the settings of Pr. 320 to Pr. 322 (RA output selection).
!
There is no need to input AU signal.
Prepare the commercial power supply in accordance with the power supply specifications of the
detector.
I003053E
Fig. 5-187:
Connection diagram multi-pump function
(alternative system, direct system, alternative direct system)
RST
UVW
JOG(X64)
10
2
5
1
4
(RIO1)FU
(RO1)OL
(RIO2)IPF
SE
MC
RIO1
(RO2)SU
(RIO3)RUN
(RO3)1A
1C
(RIO4)2A
2C
(RO4)3A
3C
RO1
MC
STF
STR
FR-A8AR
RIO1
RO2
RIO2
RO3
RIO3
RO4
RIO4
RT(X14)
RO1
RIO2
RO2
RIO3
MC
RO3
RIO4
RO4
M1
M2
M3
M4
0
24V
-
+
SD
- Sink logic
- Pr. 183 = 14, Pr. 185 = 64, Pr. 194 = 75, Pr. 193 = 71, Pr. 192 = 76, Pr. 191 = 72, Pr. 190 = 77
- Pr. 320 = 73, Pr. 321 = 78, Pr. 322 = 74
Distributed water
Pump 4
Pump 3
Pump 2
Pump 1
Supplied water
For 2-wire type
Detector
24 V DC
Power supply
Forward rotation
Power
supply
Reverse rotation
PID control
selection
PID forward/
reverse action
switchover
(Measured value) 4 to 20 mA
"
!
Setting
potentiometer
(Set point
setting)
Inverter
Option
"
"
Summary of Contents for FR-F800
Page 2: ......
Page 4: ......
Page 28: ...Related manuals Introduction 1 8 ...
Page 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Page 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 806: ...Outline dimension drawings Specifications 8 26 ...
Page 833: ......