![Mitsubishi Electric FR-F800 Instruction Manual Download Page 142](http://html.mh-extra.com/html/mitsubishi-electric/fr-f800/fr-f800_instruction-manual_1811884142.webp)
Frequently-used parameters (simple mode parameters)
Basic operation
4 - 12
Initial value for the FR-F820-00046(0.75K) or lower and FR-F840-00023(0.75K) or lower.
Initial value for the FR-F820-00077(1.5K) to FR-F820-00167(3.7K) and the FR-F840-00038(1.5K) to
FR-F840-00083(3.7K).
Initial value for the FR-F820-00250(5.5K), FR-F820-00340(7.5K), FR-F820-00126(5.5K), and FR-F840-
00170(7.5K).
Initial value for the FR-F820-00490(11K) to FR-F820-01540(55K), FR-F820-00250(11K) to
FR-F840-00770(37K).
"
Initial value for the FR-F820-01870(45K), FR-F820-02330(55K), FR-F840-00930(45K), and FR-F840-
01160(55K).
!
Initial value for the FR-F820-03160(75K) or higher and FR-F840-01800(75K) or higher.
For the FR-F820-02330(55K) or lower and FR-F840-01160(55K) or lower.
&
For the FR-F820-03160(75K) or higher and FR-F840-01800(75K) or higher.
#
Initial value for the FR-F820-00340(7.5K) or lower and FR-F840-00170(7.5K) or lower.
$
Initial value for the FR-F820-00490(11K) or higher and FR-F840-00250(11K) or higher.
'
FM denotes the initial value for the FM type inverter that has the terminal FM, and CA denotes the
initial value for the CA type inverter that has the terminal CA.
7
F010
Acceleration time
0.1 s
0–3600 s
Sets the acceleration time.
15 s
8
F011
Deceleration time
0.1 s
10 s
0–3600 s
Sets the deceleration time.
30 s
9
H000
C103
Electronic thermal
O/L relay
0.01 A
Rated
inverter
current
0–500 A
Protects the motor from heat.
Set the rated motor current.
0.1 A
&
0–3600 A
&
79
D000
Operation mode
selection
1
0
0–4, 6, 7
Select the start and frequency command
sources.
125
T022
Terminal 2
frequency setting
gain frequency
0.01 Hz 60 Hz 50 Hz
0–590 Hz
Allows the frequency at the maximum
potentiometer setting (5 V in the initial
setting) to be changed.
126
T042
Terminal 4
frequency setting
gain frequency
0.01 Hz 60 Hz 50 Hz
0–590 Hz
Allows the frequency at the maximum
current input (20 mA in the initial setting)
to be changed.
160
E440
User group read
selection
1
9999
0
0, 1, 9999
Restricts the parameters that are read by
the operation panel and the parameter
unit.
998
E430
PM parameter
initialization
1
0
0, 12, 14,
112, 114,
8009, 8109,
9009, 9109
Selects the PM motor control and set the
parameters that are required to drive a PM
motor.
999
E431
Automatic
parameter setting
1
9999
1, 2, 10, 11,
12, 13, 20,
21, 30, 31,
9999
Changes parameter settings as a batch. The
target parameters include communication
parameters for the Mitsubishi's human
machine interface (GOT) connection and
the parameters for the rated frequency
settings of 50 Hz/60 Hz.
Pr.
Pr.
group
Name
Unit
Initial value
'
Range
Application
Refer
to
page
FM
CA
Tab. 4-9:
Simple mode parameters (2)
Summary of Contents for FR-F800
Page 2: ......
Page 4: ......
Page 28: ...Related manuals Introduction 1 8 ...
Page 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Page 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 806: ...Outline dimension drawings Specifications 8 26 ...
Page 833: ......