Parameters
(A) Application parameters
FR-F800
5 - 365
Setting multiple PID functions
●
When the second PID function is set, two sets of PID functions can be switched for use. The PID
setting is selected as shown in the table below.
While Pr. 155 = "0", the second function is enabled immediately after RT signal turns ON. While
Pr. 155 = "10", the second function is enabled only during constant speed operation when RT signal
turns ON. (Refer to page 5-285 for the details.)
●
The second PID function parameters and signals function in the same way as the following
parameters and signals of the first PID function. Refer to the first PID function when setting the
second PID functions.
Pr.128 setting
(First PID setting)
Pr. 753 setting
(Second PID setting)
Pr.155
setting
RT signal
PID setting applied to the
output frequency
"0" or not applied to the
frequency
"0" or not applied to the
frequency
⎯
⎯
Control other than PID
control
"0" or not applied to the
frequency
Applied to the frequency
⎯
⎯
Second PID setting
Applied to the frequency
"0" or not applied to the
frequency
⎯
⎯
First PID setting
Applied to the frequency
Applied to the frequency
0
OFF
First PID setting
ON
Second PID setting
10
⎯
First PID setting
Tab. 5-177:
Selection of PID settings
Classification
First PID function parameters
Second PID function parameters
Pr.
Name
Pr.
Name
Parameter
127
PID control automatic switchover
frequency
754
Second PID control automatic
switchover frequency
128
PID action selection
753
Second PID action selection
129
PID proportional band
756
Second PID proportional band
130
PID integral time
757
Second PID integral time
131
PID upper limit
1143
Second PID upper limit
132
PID lower limit
1144
Second PID lower limit
133
PID action set point
755
Second PID action set point
134
PID differential time
758
Second PID differential time
553
PID deviation limit
1145
Second PID deviation limit
554
PID signal operation selection
1146
Second PID signal operation selection
575
Output interruption detection
time
1147
Second output interruption detection
time
576
Output interruption detection
level
1148
Second output interruption detection
level
577
Output interruption cancel level
1149
Second output interruption cancel level
609
PID set point/deviation input
selection
1140
Second PID set point/deviation input
selection
610
PID measured value input
selection
1141
Second PID measured value input
selection
Tab. 5-178:
Parameters for setting multiple PID functions
Summary of Contents for FR-F800
Page 2: ......
Page 4: ......
Page 28: ...Related manuals Introduction 1 8 ...
Page 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Page 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 806: ...Outline dimension drawings Specifications 8 26 ...
Page 833: ......