Parameter clear / all parameter clear
Parameters
5 - 548
5.14
Parameter clear / all parameter clear
NOTES
Set "1" to Pr.CLR "Parameter clear", ALL.CL "All parameter clear" to initialize all parameters. (Param-
eters cannot be cleared when Pr. 77 "Parameter write selection" = "1".)
Pr.CL does not clear calibration parameters or the terminal function selection parameters.
Refer to the parameter list on page A-5 for parameters cleared with this operation.
Operation
Screen at power-ON
The monitor display appears.
Changing the operation mode
Press
to choose the PU operation mode. [PU] indicator is lit.
Parameter setting mode
Press
to choose the parameter setting mode. (The parameter number read previously appears.)
Selecting the parameter number
To perform a parameter clear, turn
to
, and to perform all parameter clear, turn it to
and
press
. "
" (initial value) appears.
"
Parameter clear
Turn
to change the set value to "
". Press
to enter the setting. "
" and "
"
(
) flicker alternately after parameters are cleared.
Turn
to read another parameter.
Press
to show the setting again.
Press
twice to show the next parameter.
Tab. 5-285:
Parameter clear
Setting
Description
Pr.CLR Parameter clear
ALL.CL All parameter clear
0
Parameters are not cleared.
1
Returns parameters excluding calibration parameters
and terminal function selection parameters to their
initial values.
Returns all parameters which can be cleared including
calibration parameters and terminal function
selection parameters to their initial values.
Tab. 5-286:
Parameter clear and all parameter clear
Summary of Contents for FR-F800
Page 2: ......
Page 4: ......
Page 28: ...Related manuals Introduction 1 8 ...
Page 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Page 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 806: ...Outline dimension drawings Specifications 8 26 ...
Page 833: ......