Parameters
(T) Multi-Function Input Terminal Parameters
FR-F800
5 - 275
Continue operation at analog current input loss (Pr. 573 = "1, 4", Pr. 777)
●
When Pr. 573 = "1", operation is continued with the output frequency before the current input loss.
●
When Pr. 573 = "4" and Pr. 777 ≠ "9999", operation is continued with frequency set in Pr. 777.
●
When the start command is turned OFF during the input current loss, deceleration stop is
immediately performed, and the operation is not restored even if start command is input again.
●
When the current input is restored, the LF signal is turned OFF, and operation is performed
according to the current input.
●
External operation
●
PID control (reverse action)
I001197E
Fig. 5-128:
4mA input check during external operation (Pr. 573 = 1 or 4)
I001198E
Fig. 5-129:
4mA input check during PID control (reverse action, Pr. 573 = 1 or 4)
NOTE
When the setting is changed to continuously operate after the input current loss (Pr. 573 = "1, 4"),
the motor will operate as the frequency before loss is 0 Hz.
20 mA
4 mA
2 mA
3 mA
Output frequency
Analog input
Pr. 573 = 1: Operation continued with the frequency before being lost
Pr. 573 = 4: Operation continued with Pr. 777 setting
Input current
decrease
LF signal
Time
Return
2 mA
3 mA
4 mA
20 mA
Output frequency
Pr. 573 = 1: Operation continued with the frequency before being lost
Pr. 573 = 4: Operation continued with Pr. 777 setting
Input current
decrease
LF signal
Time
Return
PID signal
Set point (fixed)
Measured value
On during input decrease
Summary of Contents for FR-F800
Page 2: ......
Page 4: ......
Page 28: ...Related manuals Introduction 1 8 ...
Page 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Page 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 806: ...Outline dimension drawings Specifications 8 26 ...
Page 833: ......