(A) Application parameters
Parameters
5 - 358
PID automatic switchover control (Pr. 127)
●
The system can be started up more quickly by starting up without PID control activated.
●
When Pr. 127 "PID control automatic switchover frequency" is set, the startup is made without PID
control until the output frequency reaches the Pr. 127 setting. Once the PID control starts, the PID
control is continued even if the output frequency drops to Pr. 127 setting or lower.
Selection of action at a communication error and SLEEP function stop selection
(FUP signal, FDN signal,Y48 signal, Pr. 554)
●
Using Pr. 554 "PID signal operation selection", set the action when the measured value input
exceeds the upper limit (Pr. 131 "PID upper limit") or lower limit (Pr. 132 "PID lower limit"), or when
the deviation input exceeds the permissible value (Pr. 553 "PID deviation limit").
●
Set the time from when the measured value input exceeds the Pr.131 or Pr.132 setting until the
FUP or FDN signal is output in Pr. 1370 "Detection time for PID limiting operation".
●
Set Pr. 554 to select the operation when the FUP/FDN or Y48 signal is output, and the operation
when the sleep function is activated.
I001234E
Fig. 5-168:
Automatic switchover to PID control
Pr. 554 setting
Inverter operation
At FUP signal, FDN signal output
At Y48 signal output
At SLEEP operation start
0 (Initial value) Signal output only
Signal output only
Coasts to stop
1
Signal output shutoff (E.PID)
2
Signal output only
Signal output
shutoff (E.PID)
3
Signal output shutoff (E.PID)
4
Signal deceleration stop (E.PID)
Signal output only
5
Signal deceleration stop (restart)
6
Signal deceleration stop (E.PID)
Signal output
shutoff (E.PID)
7
Signal deceleration stop (restart)
10
Signal output only
Signal output only
Deceleration stop
11
Signal output shutoff (E.PID)
12
Signal output only
Signal output
shutoff (E.PID)
13
Signal output shutoff (E.PID)
14
Signal deceleration stop (E.PID)
Signal output only
15
Signal deceleration stop (restart)
16
Signal deceleration stop (E.PID)
Signal output
shutoff (E.PID)
17
Signal deceleration stop (restart)
Tab. 5-174:
Stop action at SLEEP function
Output frequency
Without
PID control
Time
PID control
Pr. 127
Summary of Contents for FR-F800
Page 2: ......
Page 4: ......
Page 28: ...Related manuals Introduction 1 8 ...
Page 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Page 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 806: ...Outline dimension drawings Specifications 8 26 ...
Page 833: ......