(D) Operation command and frequency command
Parameters
5 - 134
Command source switchover via external terminals (X67)
●
In the Network operation mode, the start command source and speed command source can be
switched over by the command source switchover signal (X67). This can be used to control signal
inputs from both the external terminals and via communication.
●
For the X67 signal, set "67" to any of Pr. 178 to Pr. 189 (input terminal function selection) to assign
the function to a control terminal.
●
When the X67 signal is OFF, the start command source and speed command source are given via
control terminals.
5.6.4
Reverse rotation prevention selection
This function can prevent reverse rotation fault resulting from the incorrect input of the start signal.
●
Set this parameter to limit the motor rotation to only one direction.
●
This parameter is valid for all of the reverse rotation and forward rotation keys of the operation
panel and of the parameter unit, the start signals (STF, STR signals) via external terminals, and the
forward and reverse rotation commands through communication.
X67 signal state
Start command source
Speed command source
Signal not assigned
According to Pr. 338
According to Pr. 339
ON
OFF
Commands from external terminals are only valid.
Tab. 5-62:
Switching of command source by the signal X67
NOTES
The ON/OFF state of the X67 signal is applied only during a stop. When the terminals are switched
during operation, the ON/OFF state is applied after a stop.
When the X67 is OFF, a reset via communication is disabled.
Changing the terminal assignment using Pr. 178 to Pr. 189 (input terminal function selection) may
affect the other functions. Set parameters after confirming the function of each terminal.
Parameters referred to
Pr. 28
Multi-speed input compensation selection
=>
Pr. 59
Remote function selection
=>
Pr. 79
Operation mode selection
=>
Pr.
Name
Initial value
Setting range
Description
78
D020
Reverse rotation prevention
selection
0
0
Both forward and reverse rotations
allowed
1
Reverse rotation disabled
2
Forward rotation disabled
Summary of Contents for FR-F800
Page 2: ......
Page 4: ......
Page 28: ...Related manuals Introduction 1 8 ...
Page 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Page 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 806: ...Outline dimension drawings Specifications 8 26 ...
Page 833: ......