Parameter List
Parameters
5 - 16
A
djus
tm
e
nt func
tion
820
G211
Speed control P gain 1
0 to 1000%
1%
25%
821
G212
Speed control integral time 1
0 to 20 s
0.001 s
0.333 s
822
T003
Speed setting filter 1
0 to 5 s, 9999
0.001 s
9999
824
G213
Torque control P gain 1 (current loop
proportional gain)
0 to 500%
1%
50%
825
G214
Torque control integral time 1 (current
loop integral time)
0 to 500 ms
0.1 ms
40 ms
827
G216
Torque detection filter 1
0 to 0.1 s
0.001 s
0 s
828
G224
Parameter for manufacturer setting. Do not set.
830
G311
Speed control P gain 2
0 to 1000%, 9999
1%
9999
831
G312
Speed control integral time 2
0 to 20 s, 9999
0.001 s
9999
832
T005
Speed setting filter 2
0 to 5 s, 9999
0.001 s
9999
834
G313
Torque control P gain 2
0 to 500%, 9999
1%
9999
835
G314
Torque control integral time 2
0 to 500 ms, 9999
0.1 ms
9999
837
G316
Torque detection filter 2
0 to 0.1 s, 9999
0.001 s
9999
Ad
d
it
io
n
a
l
func
tion
849
T007
Analog input offset adjustment
0 to 200%
0.1%
100%
A
dditio
n
al f
u
nc
ti
on
858
T040
Terminal 4 function assignment
0, 4, 9999
1
0
859
C126
Torque current/Rated PM motor current
0.01 A
9999
0 to 3600 A, 9999
860
C226
Second motor torque current/Rated PM
motor current
0.01 A
9999
0 to 3600 A, 9999
864
M470
Torque detection
0 to 400%
0.1%
150%
In
dication
fu
n
ct
io
n
866
M042
Torque monitoring reference
0 to 400%
0.1%
150%
⎯
867
M321
AM output filter
0 to 5 s
0.01 s
0.01 s
⎯
868
T010
Terminal 1 function assignment
0, 4, 9999
1
0
⎯
869
M334
Current output filter
0 to 5 s
0.01 s
⎯
0.02 s
⎯
870
M440
Speed detection hysteresis
0 to 5 Hz
0.01 Hz
0 Hz
Pro
te
c
ti
v
e
Fu
n
ct
io
n
s
872
H201
Input phase loss protection selection
0, 1
1
0
874
H730
OLT level setting
0 to 400%
0.1%
120%
110%
R
e
generation a
v
oidance
func
tion
882
G120
Regeneration avoidance operation
selection
0 to 2
1
0
883
G121
Regeneration avoidance operation
level
300 to 800 V
0.1V
DC 380 V
DC 760 V
884
G122
Regeneration avoidance at
deceleration detection sensitivity
0 to 5
1
0
885
G123
Regeneration avoidance compensation
frequency limit value
0 to 590 Hz, 9999
0.01 Hz
6 Hz
886
G124
Regeneration avoidance voltage gain
0 to 200%
0.1%
100%
Fr
e
e
pa
rame
te
rs
888
E420
Free parameter 1
0 to 9999
1
9999
889
E421
Free parameter 2
0 to 9999
1
9999
Fu
n
c
ti
o
n
Pr.
Pr.
group
Name
Setting range
Minimum
setting
increments
Initial value
Refer
to page
Cu
st
o
m
e
r
setting
FM
CA
Tab. 5-2:
Parameter overview (by number) (15)
Summary of Contents for FR-F800
Page 2: ......
Page 4: ......
Page 28: ...Related manuals Introduction 1 8 ...
Page 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Page 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 806: ...Outline dimension drawings Specifications 8 26 ...
Page 833: ......