Parameters
(N) Operation via communication and its settings
FR-F800
5 - 511
5.12.8
USB device communication
A personal computer and an inverter can be connected with a USB cable. Setup of the inverter can be
easily performed with FR Configurator2.
The inverter can be connected simply to a personal computer by a USB cable.
Changed setting value becomes valid at power ON or the inverter reset.
USB communication specifications
Pr.
Name
Initial
value
Setting
range
Description
N040
USB communication
station number
0
0 to 31
Inverter station number specification
548
N041
USB communication check
time interval
9999
0
USB communication is possible, however the inverter
will trip (E.USB) when the mode changes to the PU
operation mode.
0.1 to 999.8 s
Set the communication check time interval.
If a no-communication state persists for longer than
the permissible time, the inverter will trip (E.USB).
9999
No communication check
Specification
Description
Interface
Conforms to USB1.1 (USB2.0 full speed)
Transmission speed
12 Mbps
Wiring length
Maximum 5 m
Connector
USB mini B connector (receptacle)
Power supply
Self-powered
Recommended USB cable
MR-J3USBCBL3M (cable length 3 m)
Tab. 5-275:
USB communication specifications
I002841E
Fig. 5-244:
Connection to the USB connector
USB connector
USB cable
Summary of Contents for FR-F800
Page 2: ......
Page 4: ......
Page 28: ...Related manuals Introduction 1 8 ...
Page 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Page 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 806: ...Outline dimension drawings Specifications 8 26 ...
Page 833: ......