(N) Operation via communication and its settings
Parameters
5 - 500
Supported BACnet object
●
Analog input
R: Read only,
W: Read/Write (Commandable values not supported),
C: Read/Write (Commandable values supported)
●
Analog output
R: Read only,
W: Read/Write (Commandable values not supported),
C: Read/Write (Commandable values supported)
Values written to the objects that support the commandable values are stored in the Priority Array,
even when "Write Access Denied" is returned due to inconsistency of the writing requirements
such as the operating mode, on condition that the values are written within the setting range.
Available regardless of the operation mode, operation command source, and speed command
source.
Object
identifier
Object name
Present value
access type
Description
Unit
0
Terminal 1
R
Represents actual input voltage of terminal 1.
(The range varies depending on the Pr. 73 and
Pr. 267 settings.
–10 to +10 V (–100% to +100%),
–5 to +5 V (–100% to +100%) )
percent (98)
1
Terminal 2
R
Represents actual input voltage (or input
current) of terminal 2.
(The range varies depending on the Pr. 73 and
Pr. 267 settings.
0 to 10 V (0% to 100%),
0 to 5 V (0% to 100%),
0 to 20 mA (0% to 100%) )
percent (98)
2
Terminal 4
R
Represents actual input voltage (or input
current) of terminal 4.
(The range varies depending on the Pr. 73 and
Pr. 267 settings.
2 to 10 V (0% to 100%),
1 to 5 V (0% to 10 0%),
4 to 20 mA (0% to 100%) )
percent (98)
Tab. 5-264:
Object assignment for analog inputs
Object
identifier
Object name
Present value
access type
Description
Unit
0
Terminal FM (CA)
C
Controls actual output current level of terminal
FM/CA.
Control is available when Pr. 54 "FM/CA
terminal function selection" = "85"
.
(Setting range: 0 to 200%)
percent (98)
1
Terminal AM
C
Controls actual output voltage level of
terminal AM.
Control is available when Pr. 158 "AM terminal
function selection" = "86"
.
(Setting range: -200 to 200%)
percent (98)
Tab. 5-265:
Object assignment for analog outputs
Summary of Contents for FR-F800
Page 2: ......
Page 4: ......
Page 28: ...Related manuals Introduction 1 8 ...
Page 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Page 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 806: ...Outline dimension drawings Specifications 8 26 ...
Page 833: ......