![Mitsubishi Electric FR-F800 Instruction Manual Download Page 675](http://html.mh-extra.com/html/mitsubishi-electric/fr-f800/fr-f800_instruction-manual_1811884675.webp)
Parameters
(N) Operation via communication and its settings
FR-F800
5 - 513
GOT2000 series automatic recognition
●
When the GOT2000 series is connected, the parameters required for the GOT connection are
automatically changed by setting the automatic recognition on the GOT2000 series side.
●
Set the station number (Pr. 117 or Pr. 331) of the inverter before the automatic recognition is
performed.
●
Connect all the stations of inverters with GOT before the automatic recognition is performed. The
inverter newly added after automatic recognition is not recognized automatically. (When an
inverter is added, perform the initial setting in Pr. 999 "Automatic parameter setting" or set the
automatic recognition on the GOT side again.)
Automatic change item
Automatic change parameter
Setting value after change
PU connector connection
RS-485 terminal
connection
Communication speed
Pr. 118
Pr. 332
Depending on the setting of
the connected device on the
GOT side.
Data length/stop bit
Pr. 119
Pr. 333
Parity
Pr. 120
Pr. 334
Waiting time setting
Pr. 123
Pr. 337
CR/LF selection
Pr. 124
Pr. 341
Number of communication
retries
Pr. 121
Pr. 335
9999 (fixed)
Communication check time
interval
Pr. 122
Pr. 336
9999 (fixed)
Protocol selection
— (Pr. 549 holds the value
before the automatic
recognition.)
Pr. 549
0 (fixed to Mitsubishi inverter
protocol)
Tab. 5-276:
Automatic parameter change with GOT
NOTES
If the automatic recognition cannot be performed, initial setting in Pr. 999 is required.
For connection to a device other than the GOT2000 series, initial setting in Pr. 999 is required.
For details, refer to the GOT2000 Series Connection Manual (Mitsubishi Product).
Parameters referred to
Pr. 999
Automatic parameter setting
=>
Summary of Contents for FR-F800
Page 2: ......
Page 4: ......
Page 28: ...Related manuals Introduction 1 8 ...
Page 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Page 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 806: ...Outline dimension drawings Specifications 8 26 ...
Page 833: ......