(A) Application parameters
Parameters
5 - 400
Stirring function during the PID sleep (Pr. 1364 and Pr. 1365)
●
This function starts the pump periodically to prevent clogging of the pump while the PID output
suspension function (sleep function) is activated.
●
When the sleep function is activated and the elapsed time exceeds the Pr. 1365 "Stirring interval
time", the pump is operated at the stirring frequency (Pr. 232 or Pr. 233). The pump decelerates to
stop when the elapsed time exceeds the Pr. 1364 "Stirring time during sleep". The interval time
count for the second time onward starts after the previous deceleration stop is completed.
●
The rotation direction depends on the Pr. 232 and Pr. 233 settings.
●
The stirring signal (STIR) turns ON during the stirring operation. For the STIR signal, set "218
(positive logic)" or "318 (negative logic)" in any of Pr. 190 to Pr. 196 (output terminal function
selection) to assign the function.
●
When Pr. 579 "Motor connection function selection" = "1 or 3" (multi-pump function), the starting
order of the motors is changed when the sleep function is activated. The stirring operation during
the sleep is applied to the motor to be started first next time. For example, when the previous
starting order was M1
→
M2
→
M3
→
M4, and the next starting order of motors is M2
→
M3
→
M4
→
M1, stirring operation during the sleep will be applied to the M2 motor.
●
When the auxiliary motor starting condition is satisfied by the stirring operation during the sleep
while the multi-pump function is used, the stirring operation continues. The auxiliary motor does
not start.
I003062E
Fig. 5-196:
Stirring function during PID sleep
Stirring frequency
Rotation direction
Remarks
Pr. 232 setting
Pr. 233 setting
9999
9999
—
The stirring function during the PID sleep is
disabled.
0 to 590 Hz
Arbitrary
Command direction
Pr. 232 frequency is used for stirring.
9999
0 to 590 Hz
Opposite to the
command direction
Pr. 233 frequency is used for stirring.
Tab. 5-195:
Settings of parameters 232 and 233
NOTES
When the control switches between the first PID control and second PID control during the sleep
function, the interval time and the stirring time timer are carried over.
When the sleep function cancellation condition is satisfied, the sleep function is cancelled, and the
stirring function during the sleep is also cancelled.
Changing the terminal assignment using Pr. 190 to Pr. 196 (output terminal function selection)
may affect the other functions. Set parameters after confirming the function of each terminal.
PID
SLEEP
STIR
Output frequency
Pr. 1365
Time
Pr. 232
(Pr. 233)
ON
Interval time
Pr. 1364
Stirring time
Interval time
Stirring time
ON
ON
ON
Pr. 1365
Pr. 1364
Summary of Contents for FR-F800
Page 2: ......
Page 4: ......
Page 28: ...Related manuals Introduction 1 8 ...
Page 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Page 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 806: ...Outline dimension drawings Specifications 8 26 ...
Page 833: ......