(N) Operation via communication and its settings
Parameters
5 - 496
Communication specifications
The specifications conform to the BACnet standard of physical medium EIA-485.
Item
Description
Physical medium
EIA-485 (RS-485)
Connection port
RS-485 terminal (PU connector is not available)
Data transfer method
NRZ encoding
Baud rate
9600 bps, 19200 bps, 38400 bps, 57600 bps, 76800 bps, 115200 bps
Start bit
Fixed to 1bit
Data length
Fixed to 8bits
Parity bit
Fixed to none
Stop bit
Fixed to 1bit
Network topology
Bus topology
Communication method
Token passing (token bus)
Master-slave (only the master is available for this product)
Communication protocol
MS/TP (master-slave/token passing LAN)
Maximum connection
255 (up to 32 for one segment, addition with a repeater is available)
Node number
0 to 127
Master
0 to 127 (this product is the master)
Supported property of BACnet standard object
type
Refer to page 5-499
Supported BIBBs (Annex K)
Refer to page 5-509
BACnet standard device profile (Annex L)
Refer to page 5-509
Segmentation Not
supported
Device address binding
Not supported
Tab. 5-260:
BACnet communication specifications
NOTES
This product conforms to BACnet Application Specific Controller (B-ASC).
This product is designed for multiple master network, therefore 2-wire type connection is sup-
ported.
Summary of Contents for FR-F800
Page 2: ......
Page 4: ......
Page 28: ...Related manuals Introduction 1 8 ...
Page 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Page 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 806: ...Outline dimension drawings Specifications 8 26 ...
Page 833: ......